Maximum recommended steam pressure for 

standard units is 15 psig at 275ºF. The 

maximum recommended pressure for hot 

water applications is 150 psig at 275ºF. For 

higher operating temperatures and 

pressures, special coils and ratings are 

required. 

U

NIT 

O

PERATION

 

Most basic unit heater systems are 

controlled by a room thermostat. Install 

thermostat on an inner wall or column to 

achieve optimum control of that area. Set 

thermostat for desired temperature. 

For steam systems, a low temperature  set-

point limit could be used to prevent the fan 

from blowing cold air when there is no steam 

passing through the coil. 

Small hot water systems could have the 

circulating pump controlled directly by the 

room thermostat. Large systems may use 

zone valves to control individual unit heaters 

where constant water circulation is used on 

the pain system. 

A louvered cone air diffuser is available as 

an optional accessory for vertical unit 

heaters. 

 

 

 

 

 

 

M

AINTENTANCE

 

 

Motor Lubrication.

  Standard motors are 

pre-lubricated and normally are not 

equipped with grease fittings. For motors 

that are equipped with grease fittings, 

contact the local motor manufacturer service 

facility to obtain information on the grease or 

oil type, and the method and frequency of 

lubricating.  The frequency of lubricating will 

depend on operating conditions and length 

of running time. 

  

 

 

Unit Heaters 

Installation & Operation Manual 

3

 

www.sigmaproducts.com  Tel: (905) 453-0446   Fax: (905) 453-0675 

Warning:

 Disconnect all power, steam or 

water supplies before installing or 

servicing the unit. Do not depend on a 

thermostat or other switch as sole means 

of disconnecting power. Always 

disconnect power at the main breaker. 

Caution:

 Allow rotating fans to stop 

before servicing to avoid serious injury to 

fingers and hands. 

Rev 2 

Summary of Contents for 30-H

Page 1: ...MANUFACTURERS OF HYDRONIC HEATING PRODUCTS Unit Heaters Installation and Operation Manual www sigmaproducts com Tel 905 453 0446 Fax 905 453 0675 Rev 2...

Page 2: ...y to provide any scaffolding or other apparatus to allow service or periodic maintenance to this equipment INSTALLATION Unit Heaters Installation Operation Manual 1 www sigmaproducts com Tel 905 453 0...

Page 3: ...kept clean and free of foreign substances such as excessive joint materials etc For steam systems it is recommended that the unit be mounted level for proper condensate drainage Swing joints should b...

Page 4: ...s where constant water circulation is used on the pain system A louvered cone air diffuser is available as an optional accessory for vertical unit heaters MAINTENTANCE Motor Lubrication Standard motor...

Page 5: ...an guard motor frame and fan bolts Check the fan for clearance in the panel orifice and free rotation The heater system should be checked once per year by a qualified technician All maintenance and se...

Page 6: ...7 50 15 5 0 50 40 9 18 23 40 H 1 22 13 5 4 75 8 7 50 15 5 1 25 40 10 23 29 47 H 2 27 16 5 5 00 8 5 7 75 16 25 1 25 48 10 23 29 58 H 2 27 16 5 5 00 8 5 9 50 18 0 1 25 48 10 28 35 62 H 2 31 5 19 5 5 62...

Page 7: ...13 625 3 375 V 44 125 30 4 125 2 2 5 1 2 13 UNC 3 9 125 3 480 V 44 125 30 4 125 2 2 5 1 2 13 UNC 3 13 625 3 DIMENSIONS IN MAX MTG HT FT MODEL K L M N P R S WT LB WITHOUT LOUVER WITH LOUVER 40 V 3 11 5...

Page 8: ...FIGURE 4 TYPICAL PIPING CONNECTIONS Unit Heaters Installation Operation Manual 7 www sigmaproducts com Tel 905 453 0446 Fax 905 453 0675 Rev 2...

Reviews: