DISPLAY REMAINS AT ZERO OR SHOWS NO CHANGE --  If the display remains at zero or 

shows no change but the process is changing, check for DC voltage on the loop.  With 2 wire (4/20MA) 
instruments check with a DC voltmeter at the level instrument, by disconnecting the level instrument 
from its 2 wires and measuring across these 2 wires with a DC voltmeter for the presence of 24VDC.  
Check the diagnostic screen for analog input value. 
 
 
If DC voltage is present, reconnect the negative wire of the supply and insert a milliamp meter between 
the positive wires.  The loop should provide a signal between 4 and 20 MA.  If no current is present 
or & current exceeds 20MA consult the level instrument supplier. 
 
If DC voltage is not present check the user supplied power supply or if using the 700 DPCF/TPCF supply  
measure across terminals 24VDC and + and -.  If no 24VDC is present consult factory.  If 24VDC is 
present check field wiring between the 700 DPC and the field device and recheck ‘SCALE’ functions to 
ensure correct setup. 
  
 
 
 
 
 
 
 

NOTE:   This should be done by using the user provided circuit breaker or fuse, 
not by removing the power wires at the terminal block.  Serious injury or death 
can occur if contact is made with the incoming AC power. 

MAINTENANCE AND TROUBLE SHOOTING 
 
 

The Series 700 MM is a digital solid state device which requires no periodic maintenance. 
 
Occasional checks of the unit should be carried out for physical and mechanical security of mounting, 
terminal blocks, and electrical wiring. 
 
 

TROUBLE SHOOTING 
 

• 

UNIT ‘LOCKS UP’ --  Recycle power to the unit by removing AC power, waiting 10 seconds and 

reconnecting power. 
 

Summary of Contents for 700 MM

Page 1: ...1 VISIT OUR WEBSITE SIGMACONTROLS COM 700 SERIES MM MOTOR MONITOR INSTRUCTION MANUAL 700 MM MANUAL 042414...

Page 2: ...onitor Showing Inputs 8 100 OHM RTD Digital Output 4 Form C Relays PROGRAMMING AND INITIAL SETUP 7 Input Range Selection Terminal Block Detail Initial Setup Programming Overview Key Description DIAGNO...

Page 3: ...winding bearings overtemperature etc Provides relay outputs for motor high temp warning and motor shutdown Visual alarms LED Available Nema 4X enclosures ORDERING INFORMATION Wall Mount Nema 4X Enclos...

Page 4: ...r programmable SPDT Form C relays 5 AMP CPU Activity Monitor PROGRAMMING Menu based all parameters and setpoints are user configurable via menu prompts and user keys The preconfigured screens and pull...

Page 5: ...Master Slave CPU Activity Monitor WIRING DETAIL See Dwg 12 103 CAUTION All electrical wiring must be in accordance with all local state and national codes that apply Do not exceed the rated current o...

Page 6: ...6...

Page 7: ...s have appeared the unit will show the MAIN SCREEN which scrolls as shown below NOTE Should any channel go into WARN or ALARM modes screen will continue to scroll with the alarm message on the bottom...

Page 8: ...is designed for a fixed range sensor scaling is automatic However due to inconsistencies in some sensors a TWEAK screen is provided to make minor adjustments Use a RTD simulator to inject a known tem...

Page 9: ...advance to the Winding Setpoint Screens Use to change or press to advance to the Press the to save values and return to the Main Screen This is the temperature which brings up the HOT alarm and turns...

Page 10: ...access to program items NOTE Please make a note of the password value if changed Access to the Menus will be unavailable without the correct password Press to advance to the clock calendar settings U...

Page 11: ...nd digital common It is necessary to remove the screen panel to access this terminal block Logging occurs whenever these points are closed THE DIAGNOSTIC SCREEN The final menu item is DIAGNOSTICS This...

Page 12: ...hase A2 Tweak _________ Phase B1 Tweak _________ Phase B2 Tweak _________ Setpoints Bearing Warning Setpoint ______ Bearing Alarm Setpoint ________ Setup Password ___________ Log Interval ___________...

Page 13: ...ltage is not present check the user supplied power supply or if using the 700 DPCF TPCF supply measure across terminals 24VDC and and If no 24VDC is present consult factory If 24VDC is present check f...

Page 14: ...TURNED TO SENDER OR DISCARDED NOTE DO NOT SUBMERGE UNITS FOR CLEANING WITH CABLE CUT OR REMOVED THIS WILL ALLOW CLEANING FLUID TO ENTER HOUSING DAMAGING ELECTRONICS AND VOIDING THE WARRANTY RETURN FOR...

Reviews: