background image

2 |  RedyIndustrial_v1_2022

Terminal Assignment

     Always disconnect the power suppy before working on the terminals and plugs!

1

Terminal Assignments Modbus RTU, Power Supply & Analog Signals (Male)v

Terminals

Assignment

Description

0

Ground

Connected to Housing

Power Supply 

& Analog 

SIgnals

1

Common (-)

GND Analog Signals

2

Supply 0 Vdc

0 vdc Supply Voltage

3

24 Vdc

+24 vdc Supply Voltage

4

Output (+)

Analog Output, Measured Value

5

Setpoint (+)

Analog input, setpoint

Modbus RTU

6

Tx+

RS-485 Output (Y)

7

Tx-

RS-485 Output (Z)

8

Rx-

RS-485 Input (B)

9

Rx+

RS-485 Input (A)

Valve

15

- (Valve)

Control Valve (for MFC Option Only)

16

+ (Valve

Control Valve (for MFC Option Only)

2

M12 Plug Pin Assignments Modbus RTU, Power Supply & Analog Signals (Male)

PIN

Assignment

Wire Color

1

RS-485 B (+) (Rx+/Tx+)

White

2

Brown

3

Se

Green

4

0 Vdc

Yellow

5

Not Connected

Grey

6

RS-485 A (-) (Rx+/Tx+)

Pink

7

+24 Vdc

Blue

8

Common

Red

Pin Assignment

Available Connections

1

2

3

1

2

4

4

1

2

3

4

2

3

4

5

6

7

1

8

45°