Special functions
72
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
17
Special functions
The functions described in this chapter must be used only during commissioning
and/or maintenance. It is not allowed to use these functions during normal
operation. The following access code shall not be delivered to the customer.
17.1 Anticipated Silence Sounders
This function makes it possible to stop/start the Sounders during the pre-warning
time.
1.
Enable operating access level 2,
2.
Press and hold down "Silence buzzer" key (6), then enter the code
2 1 1 2 4 3
on the numeric keypad:
the sounders stop
3.
Press the "Silence/Re-sound Sounders" key (5)
the sounders start again
17.2 Anticipated Reset
This function makes it possible to reset the system without having to wait the end
of the programmed flooding time.
1.
Enable operating access level 2
2.
Press and hold down the « Silence buzzer » key (6), then enter
the code
2 4 4 2 1 3
on the numeric keypad:
"Pre-warning" time ends immediately and the reset can be carried out