Test functions
69
Building Technologies
A6V10257473_b_en_--.doc
Fire Safety & Security Products
01.2010
15.7 Individual output test
All the outputs, except those programmed as actuators, can be tested individually:
- The individual test of the outputs, once enabled, automatically ends after 1 mn if
no action is carried out for this period
- The outputs can be tested only one by one (duration = 3 mn max.)
During test phase:
- Alarms and faults are not indicated
- The extinguishing process cannot be started
- Programming access is not possible
- The connection with the maintenance PC cannot be enabled
Procedure
1.
Remove the front plastic cover (XC1001-A / XC1003-A only)
2.
Enable operating access level 2
3.
Press and hold down the key « Silence buzzer » (6), then enter
the code
3 4 2 1 1 2
on the keypad:
Display indicates « 0101 »
« System fault » (4), « Earth fault » (5) and « Disable » (6) led light up
alternatively, « Operating access » led (10) goes out
4.
Press the key « Silence buzzer » (6) to choose the category of the output to be
tested (represented by both digits on the left of the display):
01 = monitored outputs
02 = relay outputs
03 = driver outputs
5.
Press the « Mode select » key (8) to choose the number of the output to be
tested (represented by both digits on the right of the display)
6.
Press the « Lamp test » key (9) to start the test:
The output is enabled for 3 mn (press the « Lamp test » (9) key again to
disable it before 3 mn, if necessary)
7.
Start operations 4. to 6. again to test another output
8.
Press « Reset » the key (7) to leave the test