WT.050.130.000.UA.IM.1108
ACUTEC
™
35 SYSTEM
22
3.2.2 Range
Selection
Receivers are factory configured for the Standard Operating Range and
Setpoints as listed below.
Factory Settings of Range and Setpoints
Gas
Standard
Range
Warning
Setpoint
Alarm
Setpoint
Chlorine
0 - 10 ppm
1 ppm
3 ppm
Sulfur Dioxide
0 - 20 ppm
2 ppm
5 ppm
Ammonia
0 - 100 ppm
25 ppm
35 ppm
Display range selection is made using binary numbers to represent the
full scale operating range for the receiver. The RANGE SELECTION table,
below, provides the proper switch settings for the ranges available on each
receiver. Range selection is made using switches C1 to C4. The 4-20mA
output signal is proportional to the selected range.
Range Selection
Display Range
Switch Settings
0 - 1.00
0000
0 - 2.00
0001
0 - 3.00
0010
0 - 4.0
0011
0 - 5.0
0100
0 - 10.0
0101
0 - 20.0
0110
0 - 25.0
0111
0 - 50
1000
0 - 100
1001
0 - 200
1010
0 - 500
1011
3.2.3 Setpoint
Selection
The Warning and Alarm setpoints are factory configured to the values
shown in FACTORY SETTINGS OF RANGE AND SETPOINTS table, above,
and can be changed by using the configuration switches identified
in the DIP SWITCH FUNCTIONS chart. The Warning setpoint is set us-
ing switches A2 to A8 and the Alarm setpoint is set using switches
B2 to B8. A binary number is used to select setpoints as a percent of
operating range.