WT.050.130.000.UA.IM.1108
ACUTEC
™
35 SYSTEM
2
1.1 Technical
Data
Gas Ranges
Gas
Standard
Range
Minimum
Range
Maximum
Range
Chlorine
0 - 10 ppm
0 - 5 ppm
0 - 50 ppm
Sulfur Dioxide
0 - 20 ppm
0 - 10 ppm
0 - 100 ppm
Ammonia
0 - 100 ppm
0 - 50 ppm
0 - 500 ppm
Gas sensors are shipped factory set to standard ranges, but may be
calibrated to other ranges as shown.
Setpoints
Adjustable, 5 - 100% of Range
Enclosure Ratings
NEMA 4X (except battery enclosure)
Distance, Transmitter to Receiver 1000 ft. (maximum)
Operating Temperature
0 to 105 °F, continuous
-10 to 120 °C, intermittent
Humidity
0 - 99%, non-condensing
Power
85 - 255 VAC, 50/60 Hz, 15 W
Contacts
Alarm (configurable): 3 SPDT
Trouble: 1 SPDT
Power Failure: 1 SPDT
Contact Rating
10 A at 120 VAC, 5 A at 250 VAC,
Resistive
Battery Back-up (optional)
12 V, 4 A/hr, 6 Hrs minimum
Analog Output (optional)
4-20 mA, Isolated, 1000 ohms
maximum
Sensor Life
2 years (maximum)
Gas Generator Life
1 year
NOTE: The Auto-Test option is for indoor use only, and should only
be used with detectors set to the standard range or lower, as shown
in the GAS RANGES table. If used with higher ranges, the generator
may not produce enough gas to test the sensor.