instabus EIB

 

Technical Product Information 

April 2006 

Touch panel UP 588 

5WG1 588-2AB01  

Touch panel UP 588/11 

5WG1 588-2AB11 

Touch panel UP 588/21 

5WG1 588-2AB21 

Accessories: Design frame, anodised aluminium 

5WG1 588-8AB01 

Siemens AG 

UP 588, 6 pages 

Technical Manual 

Automation and Drives Group 

 

 

Electrical Installation Technology 

©

 Siemens AG 2006 

Update: http://www.siemens.de/gamma 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.3.1.4/1 

Product and Applications Description 

 

 

The touch panel UP 588 is a multifunctional dis-
play/control unit for the EIB. The basis of the device is an 
LC display with a resolution of 320 x 240 pixels and an 
integrated, resistive matrix with 6 x 10 fields. The dis-
play has backlighting available, which is activated dur-
ing operation and can be switched off automatically 
after an adjustable period. 

 

Touch-Panel UP 588 

5WG1 588-2AB01 

backlighting green  

AC 230V 

 

Touch-Panel UP 588/11 

5WG1 588-2AB11 

backlighting white  

AC 230V 

 

Touch-Panel UP 588/21 

5WG1 588-2AB21 

backlighting white  

AC / DC 24V 

In connection with the associated application program, 
the display unit can be used for the following functions: 
the display and operation of up to 70 EIB standard func-
tions on 7 display pages, the display of an alarm page 
with 4 alarm signals and 2 text messages as well as the 
execution of time-controlled tasks. 
The following accessories are required for the touch 
panel:  
Design frame, aluminium 5WG1 588-8AB01 
 

Application Programs 

 

01 07 Touch-Panel vision 802103 

 

display and operation of up to 70 EIB standard  
functions on 7 display pages 

 

display of an alarm page with 4 alarm signals and  
2 text messages 

 

execution of time-controlled tasks 

 

8 scene with 10 communication objects are possible  

 

display of date and time 

Installation instructions 

 

 

The device can be used for permanent interior instal-
lations in dry rooms and for insertion in flush-type 
boxes. 

 

 

Diagram 1: 

drilling jig for cavity wall box for Touch 

panel UP 588

 

 

V

 WARNING 

 

The device may only be installed and commissioned 
by an authorised electrician. 

 

The device may only be used in connection with the 
named accessories, in particular the flush-type box. 

 

230V devices which are not included with supply may 
not be inserted in the flush-type box. It is also not 
possible to loop through 230V cables. 

 

The prevailing safety and accident regulations should 
be observed. 

 

The power supply voltage may only be connected to 
the supply if the device has been fully installed. 

 

Electrical isolation should be ensured between the 
bus cable and the 230V power supply. 

 

For planning and construction of electric installations, 
the relevant guidelines, regulations and standards of 
the respective country are to be considered. 

 

 
 

 

Summary of Contents for UP 588

Page 1: ...an alarm page with 4 alarm signals and 2 text messages as well as the execution of time controlled tasks The following accessories are required for the touch panel Design frame aluminium 5WG1 588 8AB01 Application Programs 01 07 Touch Panel vision 802103 display and operation of up to 70 EIB standard functions on 7 display pages display of an alarm page with 4 alarm signals and 2 text messages exe...

Page 2: ...l display with graphic capability and backlighting Connections Bus line EIB bus terminal screwless 0 6 0 8mm solid insulation strip length 5mm Power supply Insulation strip length 6 7mm The following conductors conductor cross sections are permitted 0 5 2 5mm2 solid 0 5 1 5mm2 finely stranded Mechanical data Housing plastic Dimensions WxHxD 190 x 156 x 58mm Mounting depth in flush type box 52mm In...

Page 3: ...is inserted in the corre sponding terminal locator on the right hand side of the housing The learning button and the programming LED are located on the left next to the module slot for the bus terminal The terminal for the power supply is on the left hand side of the device The terminal must be withdrawn in order to connect the power supply cables A6 A6 for adjusting the contrast The contrast of t...

Page 4: ... the bus terminal and the power supply terminal to the cables the terminals are inserted in the corresponding openings on the touch panel Once the bus voltage has been applied the learning button can be pressed and the physical device address can be pro grammed The LED should be extinguished when the physical address has been programmed The device is then screwed into the box using the four screws...

Page 5: ... and C3 3 each with four terminal contacts Care should be taken not to damage the two test sockets C3 1 either by accidentally connecting them to the bus conductor or with the screwdriver when trying to remove the bus terminal Carefully insert the screwdriver in the wire entry slot of the grey section of the bus terminal C3 3 and pull the bus terminal C3 out of the built in device When the red sec...

Page 6: ...anel UP 588 21 5WG1 588 2AB21 Accessories Design frame anodised aluminium 5WG1 588 8AB01 Technical Manual UP 588 6 pages Siemens AG Automation and Drives Group Update http www siemens de gamma Siemens AG 2006 Electrical Installation Technology Subject to change without prior notice P O Box 10 09 53 D 93009 Regensburg 2 3 1 4 6 Notes ...

Reviews: