background image

INTRODUCTION

Thank you for choosing the Siemens TPS9 Transient Voltage
Surge Suppressor.

This manual provides instructions for installing the TPS9
Transient Voltage Surge Suppressor (TVSS). The TPS9 TVSS
(Figure 1) can be mounted three ways. The preferred method
of installation is to mount the TVSS directly to the outside of
the electrical distribution equipment using the integral chase
nipple on the body of the TVSS. It can also be installed against
a panel/wall using installer supplied hardware, or it can be
installed using an optional Flush Mount Kit. The latter two
methods require use of additional conduit and hardware (not
provided).

Please read and understand all information in this manual prior
to installation. The procedures contained herein are not
intended to supersede local or national electrical codes. 

Check

all applicable electrical codes to ensure compliance.

 In all

instances, local and national electrical code requirements are
to be followed.

The TPS9 is a single port parallel TVSS designed for service
entrance and downstream electrical distribution equipment
applications. The TVSS uses a chase nipple for installation, and
offers 80kA, 100kA, 120kA, or 150kA per phase surge current
capabilities.

The TPS9 provides protection from damaging transient volt-
age surges and spikes. Proper installation is imperative to maxi-
mize the effectiveness and overall performance of this device.

This device must be installed by a licensed electrician.

 The

electrician should follow the steps outlined in this manual to
insure proper installation.

Note:

  Siemens products are extensively tested to industry stan-

dards as set by IEEE C62.41 and C62.45, for Categories A, B,
and C. The TPS9 is listed to the most recent edition of UL 1449.

This product is suitable for installation on  electrical distribu-
tion equipment capable of delivering not more than 200,000
rms symmetrical amperes.

This device features internal overcurrent and overtemperature
protection that will disconnect affected surge protection com-
ponents at the end of their useful life but will maintain power
to the load - now unprotected. If this situation is undesirable
for the application, follow these instructions for servicing or
replacing the device.

During installation into an electrical system, the TPS9 must NOT
be energized until the electrical system is installed, inspected
and tested. Confirm that N-G bonding is per NEC. All conduc-
tors must be connected and functional, including neutral (if
required). The voltage rating of the device and system must
always be verified before energizing the TVSS.

PARTS LIST AND INSPECTION

Items included in the package consist of the following:

1 TPS9 Transient Voltage Surge Suppressor.

1 User’s Manual (this document).

If the Flush Mount Kit was ordered, additional parts are sup-
plied as follows:

1 Flush Mount Panel

1 Flush Mount Installation Instructions

4 Pan-head Screws

Carefully inspect each item in the package for signs of damage.
If damage is found, please contact Siemens TPS Technical Sup-
port: 1.888.333.3545. For more information about this  product
or other Siemens products, visit www.sea.siemens.com.

SAFETY INFORMATION

This section provides pertinent safety information that must
be considered before installing the TVSS.

Do not install this device during a lightning storm.

This device is rated NEMA 4X. Suitable for indoor and
outdoor applications.

Do not install the surge protector in a hot or excessively
moist location.

Other safety considerations are as listed on the
following page:

Page 1

Failure to follow the guidelines in this manual can lead to
abnormally high voltage being applied to the TVSS. This may
cause the TPS9 unit to become inoperative. The warranty does
not cover an incorrectly installed device.

Failure to disconnect the TVSS during elevated voltage testing
will result in damage to the suppression components and/or
other electronic components (see Safety Information). 

Do not

high potential test the distribution system with the TVSS
connected.

V

WARNING

Confirm XO N-G Bonding at Upstream Transformer

Do Not Hi-Pot Test TVSS

Resulting Damage is Not Covered Under Warranty

Summary of Contents for TPS 9

Page 1: ...s TPS 9 Transient Voltage Surge Suppressor User s Manual ...

Page 2: ... the service entrance equipment is not bonded to ground in accordance with the National Electrical Code NEC TESTING HIGH VOLTAGE TESTING DO NOT HI POT TEST Any factory or on site testing of power distribution equipment that exceeds the normal operating voltage such as high potential insulation testing or any other tests where the suppression components will be subjected to voltages higher than the...

Page 3: ...on that will disconnect affected surge protection com ponents at the end of their useful life but will maintain power to the load now unprotected If this situation is undesirable for the application follow these instructions for servicing or replacing the device During installation into an electrical system the TPS9 must NOT be energized until the electrical system is installed inspected and teste...

Page 4: ...round wire to the electrical distri bution equipment ground Install the distribution equipment cover Note Conducting dielectric and or high potential testing will cause internal damage to the TVSS unit DO NOT per form dielectric or high potential tests with the phase or neutral TVSS wires connected Apply power to the distribution equipment Depending on the TPS9 model either 1 single phase applicat...

Page 5: ... High Leg Delta Phase C Black TPS9 TVSS 0 0 0 0 0 0 Distribution Equipment Metal Wall of Distribution Equipment 1234 1234 20 Amp Breaker Figure 2 Typical Parallel Connections Breaker Panel Interconnecting Wiring Minimize Length Avoid Sharp Bends Gently Twist Conductors Together CONDUCTING DIELECTRIC AND OR HI POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS UNIT AND WILL VOID THE UNITS WARRANTY...

Page 6: ...lice latches to the bottom portion of the butt splice The enclosed label should be placed under the LED for reference Plan your installation for adequate label space After installation test the Green LED by energizing then deenergizing the SPD and verifying that the LED turns on and off appropriately An alternate test is to deenergize just one phase CONNECTING TO OPTIONAL DRY CONTACTS IF EQUIPPED ...

Page 7: ... s e h c n i 6 3 e p y T n o i t a l l a t s n I e l p p i N e s a h C s v h t g n e L e r i W d n a e m i T e s n o p s e R e g a t l o V h g u o r h T t e L d n o c e s o n a n 1 e r i w f o m c 7 1 3 t o o f 1 0 2 8 A k 3 V k 6 t o o f r e p s t l o v 5 7 1 e h t o t d e d d a e r a s d n o c e s o r c i m e g a t l o v p m a l c d n a e z i S e r i W e u q r o T n o i t a l l a t s n I s b l n...

Page 8: ...4 4114 ext 1234 seainfo icn siemens com 2006 Siemens Energy Automation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice Order PBOM 020205 Rev B 2 5M100DW ...

Reviews: