background image

CONNECTING TO OPTIONAL REMOTE INDICATOR IF EQUIPPED
(“R” SUFFIX NEAR END OF MODEL NUMBER)

This option includes a supplemental diagnostic LED that can be
mounted in a conspicuous location.  For example, assume that
the SPD is mounted such that it is not readily visible.  A Remote
Indicator can provide visual indication of correct operation.

Operation is straightforward: Green LED On = SPD is OK.  If the
LED is out, the SPD has failed; power is not present, or one or
more phases are not energized.

The Green LED assembly includes two pre-attached wires and
two butt-splice connectors.  The SPD includes two yellow 18 AWG
wired, pre-wired through the SPD’s nipple mounting connection.

Pre-Plan the installation per normal Installation Instructions.
Note that the LED assembly and butt-splice connectors are not
weather resistant and should be protected accordingly.

Mount the LED assembly in an appropriate conspicuous location.
Drill a 1/4" diameter hole at the mounting location. Remove the
hex nut from the back side of the LED assembly and feed the
LED indicator wires through the hole. Install the hex nut.

Butt-splice the wires (polarity does not matter) from the LED
wiring assembly to the yellow SPD wires by inserting one end of
each LED wiring assembly lead into the butt-splice (supplied).
Squeeze the metal contact of the butt-splice downward. Ensure
the wires cannot be pulled out of the butt-splice.  Fold the cover
of the butt-splice over the metal contact until the cover of the
butt-splice latches to the bottom portion of the butt-splice.

The enclosed label should be placed under the LED for reference.
Plan your installation for adequate label space.

After installation, test the Green LED by energizing, then
deenergizing the SPD, and verifying that the LED turns on and
off appropriately. An alternate test is to deenergize just one
phase.

CONNECTING TO OPTIONAL DRY CONTACTS IF EQUIPPED
(“D” SUFFIX NEAR END OF MODEL NUMBER)

The Dry Contact option allows for external evaluation of the
SPD’s operating condition.  A Form C contact changes state
during inoperative conditions, including loss of power, either
in full, or loss of any individual phase. This can be configured
for either Normally Open, or Normally Closed indication.

Connections are made via two of the three 18 AWG wires, pre-
wired through the SPD’s nipple mounting connection.  There is
no terminal block connection (ensures cost-effective NEMA 4X
compliance).  Dry Contact wires are color coded per below and
are approximately 5 feet (1.5m) in length.  Do not mistake the
SPD power connection conductors for the Dry Contact wires.
Internal electrical contacts are rated 5A, 120 VAC.

Color code of Dry Contact wires when energized:

18 AWG RED - Normally Closed

18 AWG GREY - Common

18 AWG BLUE - Normally Open

Typical Installation:

For Normally Closed: Use Red and Grey wires

For Normally Open:  Use Blue and Grey wires

After installation, contacts can be tested by energizing, then
deenergizing the SPD, and verifying that contacts change state.
An alternate test is to deenergize just one phase.

Page 4

V

WARNING

Confirm XO N-G Bonding at Upstream Transformer

Do Not Hi-Pot Test TVSS

Resulting Damage is Not Covered Under Warranty

Summary of Contents for TPS 9

Page 1: ...s TPS 9 Transient Voltage Surge Suppressor User s Manual ...

Page 2: ... the service entrance equipment is not bonded to ground in accordance with the National Electrical Code NEC TESTING HIGH VOLTAGE TESTING DO NOT HI POT TEST Any factory or on site testing of power distribution equipment that exceeds the normal operating voltage such as high potential insulation testing or any other tests where the suppression components will be subjected to voltages higher than the...

Page 3: ...on that will disconnect affected surge protection com ponents at the end of their useful life but will maintain power to the load now unprotected If this situation is undesirable for the application follow these instructions for servicing or replacing the device During installation into an electrical system the TPS9 must NOT be energized until the electrical system is installed inspected and teste...

Page 4: ...round wire to the electrical distri bution equipment ground Install the distribution equipment cover Note Conducting dielectric and or high potential testing will cause internal damage to the TVSS unit DO NOT per form dielectric or high potential tests with the phase or neutral TVSS wires connected Apply power to the distribution equipment Depending on the TPS9 model either 1 single phase applicat...

Page 5: ... High Leg Delta Phase C Black TPS9 TVSS 0 0 0 0 0 0 Distribution Equipment Metal Wall of Distribution Equipment 1234 1234 20 Amp Breaker Figure 2 Typical Parallel Connections Breaker Panel Interconnecting Wiring Minimize Length Avoid Sharp Bends Gently Twist Conductors Together CONDUCTING DIELECTRIC AND OR HI POTENTIAL TESTING WILL CAUSE INTERNAL DAMAGE TO TPS UNIT AND WILL VOID THE UNITS WARRANTY...

Page 6: ...lice latches to the bottom portion of the butt splice The enclosed label should be placed under the LED for reference Plan your installation for adequate label space After installation test the Green LED by energizing then deenergizing the SPD and verifying that the LED turns on and off appropriately An alternate test is to deenergize just one phase CONNECTING TO OPTIONAL DRY CONTACTS IF EQUIPPED ...

Page 7: ... s e h c n i 6 3 e p y T n o i t a l l a t s n I e l p p i N e s a h C s v h t g n e L e r i W d n a e m i T e s n o p s e R e g a t l o V h g u o r h T t e L d n o c e s o n a n 1 e r i w f o m c 7 1 3 t o o f 1 0 2 8 A k 3 V k 6 t o o f r e p s t l o v 5 7 1 e h t o t d e d d a e r a s d n o c e s o r c i m e g a t l o v p m a l c d n a e z i S e r i W e u q r o T n o i t a l l a t s n I s b l n...

Page 8: ...4 4114 ext 1234 seainfo icn siemens com 2006 Siemens Energy Automation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice Order PBOM 020205 Rev B 2 5M100DW ...

Reviews: