![Siemens SIWAREX FTC Device Manual Download Page 45](http://html.mh-extra.com/html/siemens/siwarex-ftc/siwarex-ftc_device-manual_1265490045.webp)
W
EIGHING
F
UNCTIONS AND
P
ARAMETERS
Name
Type
Address
Default
Range of Values / Meaning
Reference
Characteristic value
range
BYTE
DBB036
2
1: Characteristic value to 1mV/V
2: Characteristic value to 2mV/V
4: Characteristic value to 4mV/V
101: Characteristic value +/- 1mV/V (force
measurement, bi-directional)
102: Characteristic value +/- 2mV/V (force
measurement, bi-directional)
104: Characteristic value +/- 4mV/V (force
measurement, bi-directional)
Other definitions not permitted.
(5) Filter
Filter sequence
BYTE
DBB037
0
Bit 0 :
0: Average value filter before digital filter
1: Digital filter before average value filter
Bits 1 to 7 not set
Type of low pass filters
BYTE
DBB038
0
0: critically damped
1: Bessel filter
2: Butterworth filter
Other definitions not permitted.
Limit Frequency
BYTE
DBB039
4
0: No filter
1: fg = 20Hz
2: fg = 10Hz
3: fg = 5Hz
4: fg = 2Hz
5: fg = 1Hz
6: fg = 0.5Hz
7: fg = 0.2Hz
8: fg = 0.1Hz
9: fg = 0.05Hz
Other definitions not permitted.
Depth of
average value filter
INT
DBW040
10
[0 ... 250] x 10 ms
0: Average value filter deactivated
Other definitions not permitted.
(1) Adjustment parameter
I
0
Scale Name
STRING
[10]
DBB042 „SIWAREX
XX“
Number of weight ranges
BYTE DBB056 1
1
Range
2 Ranges
3 Ranges
Other definitions not permitted.
Scale type
Activate zero setting
upon start-up
Activated zero setting at
start-up, if scale is tared
Automatic zero
adjustment
BYTE DBB057 0
0
0
0
Bit 0::
0: Multi-range scale
1: Multi-resolution scale
Bit 1:
0: Switch-on zero setting device switched off;
1: Switch-on zero setting device switched on
Bit 2:
0: Switch-on zero setting, not when tare
0
1: Switch-on zero setting performed with tare
0
Bit 3:
0: Zero tracking device switched off;
1: Zero tracking device switched on
Bit 4 - 7 not set
(2) Calibration parameter
II
Minimum weight for
Weighing range 1
REAL DBD058
1
SIWAREX FTC
5-33
Summary of Contents for SIWAREX FTC
Page 1: ...SIWAREX FTC Device Manual Status 10 2010 Module for Belt scale ...
Page 12: ......
Page 134: ...11 Empty 11 122 SIWAREX FTC ...