![Siemens SIWAREX FTC Device Manual Download Page 142](http://html.mh-extra.com/html/siemens/siwarex-ftc/siwarex-ftc_device-manual_1265490142.webp)
14.11 Electrical-, EMC- and Climatic Requirements
14.11.1 Electrical Protection and Safety Requirements
Requirement met
Standards
Comments
Safety regulations
EN60204; DIN VDE 0113;
IEC 1131; UL 508;
CSA C22.2 No.142;
FM class I, Div.2;
UL/CSA
UL-/CSA-/FM Zone 2
certification upon request
Protection class
VDE 0106 Part 1
IEC 536
Protection class I, with
protective conductor
IP protection
DIN 60529
IEC 529
in S7 frame: IP20
only SIWAREX FTC: IP10
Air and creepage distances
IEC 1131
UL508
CSA C22.2 No.142
Surge category II
Pollution degree 2
Circuit board material IIIa
Circuit track spacing 0.5 mm
Isolation test
IEC 1131-2: 1992
CSA C22.2 No.142
Rated voltage 24 V
Test voltage 500 V DC
Fire and burn protection
for ”Open Type Controller”:
IEC 1131-2: 1992; UL 508
Material
SN 36350 (3.93)
Table 14-11
Data: Electrical Protection and Safety Requirements
14.11.2 Electromagnetic Compatibility
interference emission
(industrial use)
: EN 61000-6-4
Comments Standard Limit
values
Emission of radio interference
(electromagnetic fields)
IEC 61131-2
EN 55011 Class A, Group 1
30 – 230 MHz: < 40dB(
V/m) Q
230-1000MHz: < 47dB(
V/m) Q
Emission on power supply
lines
IEC 61131-2
EN 55011 Class A, Group 1
EN 55014
14-130