Module errors
If an incorrect module ID of the connected DP slave is read from the block, output
QModF
will
be set. The Quality Codes are set to 16#00 as with the higher-level error.
5.3.5
Messaging of FbMag6T
Messaging
This block does not offer messaging.
5.3.6
I/Os of FbMag6T
Input parameters
Parameter
Description
Type
Default
AVolFlow
Volume flow (AI) address
INT
-1
Addr
Addresses in the process image
STRUCT
1)
-1
SubnTyp
1 = external DP interface
BOOL
0
RackF
1 = DP slave failure (rack fault)
BOOL
0
SelStrInputs
0 = I/O output data originate from the
CyclData structure
1= I/O output data originate from inputs
SetTot1/2, ModeTot1/2, DCtr, DSetP,
DComp and their QualityCodes
BOOL
0
SetTot1
Totalizer 1: 16#01 = Reset command
transferred to the module (SET_TOT
from HW Config)
BYTE
16#16#0000
ModeTot1
Totalizer 1: Command transferred to
the module (MODE_TOT from HW Con‐
fig)
BYTE
16#00
SetTot2
Totalizer 2: 16#01 = reset command
output to the module (SET_TOT from
HW Config)
BYTE
16#00
ModeTot2
Totalizer 2: Command transferred to
the module (MODE_TOT from HW Con‐
fig)
BYTE
16#00
DCtr
Dosing unit: Command transferred to
the module (B_CTR from HW Config):
BYTE
16#00
DSetP
Setpoint of the dosing unit (SETP)
REAL
0.0
QCDSetP
Signal status for the setpoint of the dos‐
ing unit
BYTE
16#00
DComp
Compensation of the dosing unit
(COMP)
REAL
0.0
SITRANS F M MAG 6000
5.3 FbMag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
143
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...