Operating
6.6 Adjusting the blanking value
SITRANS LU180
30
Operating Instructions, 06/2016, A5E37100674-AA
6.6
Adjusting the blanking value
To change the stored blanking value, go to the 'bL' display (as described in Adjustments
(Page 27)), and proceed as follows:
1.
Press the "20" key to increase the blanking value, or the "4" key to decrease it until the
correct value is displayed.
2.
Release the key. The display automatically returns to the Run mode (6 secs).
3
seconds
Indicates that the device is now in blanking mode.
The stored blanking value is shown
(for example 0.25 m)
Press “20” to increase blanking value
(i.e. 0.36 m)
Press “4” to decrease the blanking value
(i.e. 0.35 m)
6
seconds
The new blanking value is shown.
6.7
Speed of response
The speed of response adjustment allows the user to collectively set a number of operating
parameters.
measurement response: is the limit to which the SITRANS LU180 will be able to keep up
with rates of change. If the unit's measurement cannot keep up
with the rate of level change, set the adjustment from '1' to '2'. If it
still cannot keep up with the rate of level change, set the adjust-
ment option to '3'. Avoid choosing an option that is too fast for your
application.
agitator discrimination: discriminates between agitator blades in motion, and the material
(target) surface.
Summary of Contents for Sitrans LU-180
Page 1: ...Operating Instructions LU 180 Sitrans LU 180 Edition 06 2016 Ultrasonic Transmitters ...
Page 7: ...Introduction SITRANS LU180 6 Operating Instructions 06 2016 A5E37100674 AA ...
Page 9: ...Description SITRANS LU180 8 Operating Instructions 06 2016 A5E37100674 AA ...
Page 37: ...Troubleshooting SITRANS LU180 36 Operating Instructions 06 2016 A5E37100674 AA ...
Page 41: ...Technical data 8 7 Approvals SITRANS LU180 40 Operating Instructions 06 2016 A5E37100674 AA ...