Operating
6.2 Calibration, scrolling method
SITRANS LU180
28
Operating Instructions, 06/2016, A5E37100674-AA
6.2
Calibration, scrolling method
The 4 and 20 mA calibration values can be selected where reference levels, either from the
material in the vessel or from a target, cannot be provided. This method can also be used to trim
the output levels obtained by the Calibration: reference method (Page 24)
To change the stored calibration value, obtain the 'c 4' or 'c 20' display. The calibration value
may be increased by pressing the "20" key or decreased by pressing the "4" key. When the
display has scrolled to the desired value, stop pressing the key. The display automatically
reverts to the Run mode (6 secs).
Note
For faster scrolling, hold the key, and release it when the appropriate value is shown.
6.3
4 mA calibration
4 mA calibration initiated
view stored 4 mA calibration value
(i.e. 4.50 m)
press ”20” to increase to new calibration value
(i.e. 4.60 m)
new calibration value
Summary of Contents for Sitrans LU-180
Page 1: ...Operating Instructions LU 180 Sitrans LU 180 Edition 06 2016 Ultrasonic Transmitters ...
Page 7: ...Introduction SITRANS LU180 6 Operating Instructions 06 2016 A5E37100674 AA ...
Page 9: ...Description SITRANS LU180 8 Operating Instructions 06 2016 A5E37100674 AA ...
Page 37: ...Troubleshooting SITRANS LU180 36 Operating Instructions 06 2016 A5E37100674 AA ...
Page 41: ...Technical data 8 7 Approvals SITRANS LU180 40 Operating Instructions 06 2016 A5E37100674 AA ...