Operating
6.9 Fail-safe
SITRANS LU180
32
Operating Instructions, 06/2016, A5E37100674-AA
6.9
Fail-safe
In the event a loss of echo or fault condition exceeds the 'Waiting' period (see Speed of
response (Page 30), or Fail-safe timer (Page 33)), the '?' icon appears and one of the following
fail-safe defaults is immediately effected.
SP
default
mA
p
mA
i
reading
1
full
22
4
hold
2
empty
4
22
hold
3*
hold
hold
hold
hold
p = proportional span
i = inversely proportional span
* = factory setting
6.10
Adjusting the fail-safe setting
To change the fail-safe setting, go to the 'FLS'' display (as described in Adjustments (Page 27)),
and proceed as follows:
1.
Press the "20" key to scroll forward through the available values (1-2-3), and press the "4"
key to scroll backwards.
2.
Once you have reached the appropriate value, stop pressing the key. The display
automatically returns to the Run mode (6 secs).
3
seconds
Indicates that the device is now in fail-safe mode.
The current option is shown
(i.e. full)
Press “20” for option 2
(i.e. empty)
6
seconds
Option 2 has now been selected.
Summary of Contents for Sitrans LU-180
Page 1: ...Operating Instructions LU 180 Sitrans LU 180 Edition 06 2016 Ultrasonic Transmitters ...
Page 7: ...Introduction SITRANS LU180 6 Operating Instructions 06 2016 A5E37100674 AA ...
Page 9: ...Description SITRANS LU180 8 Operating Instructions 06 2016 A5E37100674 AA ...
Page 37: ...Troubleshooting SITRANS LU180 36 Operating Instructions 06 2016 A5E37100674 AA ...
Page 41: ...Technical data 8 7 Approvals SITRANS LU180 40 Operating Instructions 06 2016 A5E37100674 AA ...