SITRANS LG240 - Operating Instructions
44286-EN-171021
Menu
Menu item
Default value
Setup
Damping - Level
0.0 s
Damping - Interface
0.0 s
Setup
Linearisation type
Linear
Linearisation - Socket correction
0 mm
Linearisation - Vessel height
Probe length
Setup
Scaling variable - Level
Volume in l
Scaling unit - Level
Litres
Scaling format - Level
Without decimal positions
Scaling level - 100 % corresponds to
100
Scaling level - 0 % corresponds to
0
Scaling variable - Interface
Volume
Scaling unit - Interface
Litres
Scaling format - Interface
Without decimal positions
Scaling interface - 100 % corresponds to
100
Scaling interface - 0 % corresponds to
0
Setup
Current output, output variable
Lin. percent - Level
Current output - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output - Reaction in case of fault
≤ 3.6 mA
Current output - Min.
3.8 mA
Current output - Max.
20.5 mA
Current output 2 - Output variable
Distance - Level
Current output 2 - Output characteristics
0 … 100 % correspond to
4 … 20 mA
Current output 2 - Reaction in case of fault
≤ 3.6 mA
Current output 2 - Min.
3.8 mA
Current output 2 - Max.
20.5 mA
Menu - Display
Menu
Menu item
Default value
Display
Language
Selected language
Displayed value 1
Filling height
Displayed value 2
Electronics temperature
Display format 1
Automatically
Display format 2
Automatically
Backlight
Switched on
Summary of Contents for SITRANS LG240
Page 2: ...2 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Page 85: ...Notes 85 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Page 86: ...Notes 86 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...
Page 87: ...Notes 87 PBD 51041038 SITRANS LG240 Operating Instructions 44286 EN 171021 ...