SITRANS LG240 - Operating Instructions
44286-EN-171021
For non-linear vessel forms, enter the vessel height and the socket
correction.
For the vessel height, you have to enter the total height of the vessel.
For the socket correction you have to enter the height of the socket
above the upper edge of the vessel. If the socket is lower than the up-
per edge of the vessel, this value can also be negative.
+
h
D
- h
Fig. 21: Vessel height and socket correction value
D Vessel height
+h Positive socket correction value
-h Negative socket correction value
In the menu item "
Current output mode
" you determine the output
characteristics and reaction of the current output in case of fault.
The default setting is output characteristics 4 … 20 mA, fault mode
< 3.6 mA.
Setup - Current output,
mode