Certificates
B.2 Instructions specific to hazardous area installations
Transducers
Compact Operating Instructions, 09/2021, A5E43390688-AC
55
Specific conditions of use
The apparatus shall only be supplied from a circuit containing a suitably rated fuse having a
breaking capacity of at least 1500 A.
Parts of the enclosure may be non-conducting and may generate an ignition-capable level of
electrostatic charge under certain extreme conditions. The user should ensure that the
equipment is not installed in a location where it may be subjected to external influences,
which might cause a build-up of electrostatic charge on non-conducting surfaces.
Any open face of the XPS-10, XPS-15 or XPS-30 Transducer shall only be installed so that the
face is not substantially subjected to light.