Commissioning
6.6 Commissioning via local display
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
64
Operating Instructions, 08/2017, A5E37367739-AC
Inputs/Outputs wizard
The Inputs and outputs wizard will guide you through setup of inputs and outputs on the
available channels. The availability of channels 3 and 4 depends on the product
configuration.
Inputs/Outputs wizard
First you must set the output functionality you want the channel to operate. Choose between
Off, Current output, Frequency output, Pulse output, or Status output, Digital input or Current
input.
Channel 2 provides output functionality only.
Channel 3 and 4 provide input or output functionality.
If one of the channels 3 or 4 is configured to relay the functionality of this channel is reduced
to Status output.
Inputs/Outputs
Current output - channels 2 to 4
Current output - channels 2 to 4
The Current output can be configured to 0...20 mA or 4...20 mA. You can assign a process
value to the current, set the direction, the damping value, the lower range value, the upper
range value, and the fail-safe behaviour.