Technical data
9.2 Sensor technical data
SITRANS DA400 for material flow monitoring with protection against explosion
Operating Instructions, 09/2007, A5E00841152-01
83
Electrical data
Protection type - intrinsically safe EEx ia IIC
Signal and supply electrical circuit (unconnected
cable end)
Only for connection to approved intrinsically safe
electrical circuits with the following maximum
values:
•
Maximum voltage U
i
6 V
•
Maximum current I
i
204 mA
•
Maximum power P
i
200 mW
•
Internal capacity C
i
≤ 200 nF
•
Internal inductance L
i
≤ 500 μH