![Siemens SITRANS DA400 Operating Instructions Manual Download Page 42](http://html.mh-extra.com/html/siemens/sitrans-da400/sitrans-da400_operating-instructions-manual_378305042.webp)
Operation
6.3 Measuring menu
SITRANS DA400 for material flow monitoring with protection against explosion
42
Operating Instructions, 09/2007, A5E00841152-01
6.3.4.2
Simulation mode
Introduction
The simulation mode supports the commissioning of the device. In simulation mode, you can
check the following without real measured values:
●
The correct setting of the alarm thresholds.
●
The correct parameterization of the digital outputs.
In simulation mode, a simulated measured value is displayed in the digital display, which is
adjustable with the and buttons.
Note
Adjusting simulated measured values
A acoustic emission sensor does not need to be connected to simulate a measured value.
Condition
The measurement channel must be in simulation mode. The measurement channel is in
simulation mode if the parameter P.1 to P.4 associated with the measurement channel is set
to "SIMU".
Elements of the digital display in simulation mode
The following figure shows the elements of the digital display:
Figure 6-6
Digital display simulation mode, acoustic channel
35.0
Simulated measured value in dB; flashes if main alarm received
1/So1
Set measured channel 1
SIMU
Note that the simulation mode is active.
Procedure
In order to simulate the measured values, proceed as follows: