General safety notes
2.4 Measures
SITRANS DA400 for material flow monitoring with protection against explosion
10
Operating Instructions, 09/2007, A5E00841152-01
2.4
Measures
For the sake of safety, the following precautions must be observed:
WARNING
"Intrinsically safe" protection type
"Intrinsically-safe" devices lose their certification as soon as they are operated on circuits
which do not correspond with the test certification valid in their country. The device's
protection level "ia" is reduced to "ib" when intrinsically safe electrical circuits with
protection level "ib" are connected.
Protection type "limited energy" nL (zone 2)
Devices with "limited energy" may be connected and disconnected while in operation.
Protection type "non-sparking" nA (zone 2)
Devices with "non-sparking" protection may only be connected and disconnected when off
circuit.
CAUTION
Electrostatic Sensitive Devices (ESD)
This device contains electrostatic sensitive devices. Electrostatic sensitive devices may be
destroyed by voltages that are undetectable to a human. Voltages of this kind occur as
soon as a component or an assembly is touched by a person who is not grounded against
static electricity. The damage to a module as a result of overvoltage cannot usually be
detected immediately. It may only become apparent after a long period of operation.
2.5
Qualified Personnel
Qualified personnel are people who are familiar with the installation, mounting,
commissioning, and operation of the product. These people have the following qualifications:
●
They are authorized, trained or instructed in operating and maintaining devices and
systems according to the safety regulations for electrical circuits, high pressures and
aggressive as well as hazardous media.
●
For explosion-proof devices: They are authorized, trained, or instructed in carrying out
work on electrical circuits for hazardous systems.
●
They are trained or instructed in maintenance and use of appropriate safety equipment
according to the safety regulations.