Technical data
9.1 Device technical data
SITRANS DA400 for material flow monitoring with protection against explosion
Operating Instructions, 09/2007, A5E00841152-01
79
Output
Digital outputs
6
•
Binary outputs
Clamps 31 and 32
Clamps 41 and 42
Clamps 51 and 52
Clamps 61 and 62
Clamps 71 and 72
Clamps 81 and 82
•
Signal status Low (no response)
≤ 1.2 mA (Source: DIN 19234)
•
Signal status High (no response)
≤ 2.1 mA (Source: DIN 19234)
For connection to intrinsically safe switching amplifiers according to DIN 19234 with:
•
Maximum supply voltage U
i
≤ 15.5 V
•
Maximum short circuit current I
i
≤ 25 mA
•
Maximum power P
i
≤ 64 mW
•
Internal capacity C
i
≤ 5.2 nF
•
Internal inductance L
i
Negligible
Rated conditions
Installation conditions
Vertical wall mounting, cables fed in from below
Climate class
Class 4K4 according to EN 60721-3-4
Installation site
Zone 1 or zone 2
Mechanical load
Class 4M3 according to EN 60721-3-4
Degree of protection according to EN 60 529
IP65
Electromagnetic compatibility
•
Spurious emission and interference immunity According to EN 61326