SITOP UPS 500S 

A5E38474162, 08.2016 

 

SITOP UPS 501S 

 

 

 

English

 

!

 

WARNINGS

 

Only properly qualified personnel may work on or around this equipment. 

The successful and safe operation of this equipment is dependent on proper handling, storage and installation. Correct functioning is also 

dependent on the use of SITOP ultra modules 

 

    

 

CAUTION 

Only trained personnel may open the unit. 

Electrostatically sensitive devices (ESD)

 

    

 

Disposal Guideline 

Packaging and packing aids can be recycled and should always be disposed of for reuse. 

The product itself shall not be disposed of as normal domestic waste.

 

Description and Design  

The DC-UPS is a chassis unit in the SITOP power product range for mounting on a DIN rail of type DIN EN 50022-35x15/7.5. 

The basic units and the expansion modules must be installed in accordance with the applicable DIN/VDE specifications or pertinent regulations in the country of 

installation. 

It buffers a proportion of the load current (max. 15A) of 24V load current supplies in the SITOP  range. 

Input "Input L+" on the DC-UPS basic units must be connected to output L+ of the 24V DC power supply unit and input "Input M" to output M of the power supply unit. It 

is possible to connect max. 3 expansion modules via the connectors X10 and X30. The loads to be buffered are supplied via outputs "Output L+" and "Output M" on the 

DC-UPS basic unit with the voltage connected to the input. If the 24V DC supply voltage fails or drops below the set cut-in threshold, the expansion module or the 

internal capacitors are connected in to supply the loads.  

The cut-in threshold, charging power and the buffering time can be set via DIP-switches. A switch is provided for setting a defined buffering (stored energy) time with 

subsequent disconnection (see Settings), one switch for bridging the ON/OFF circuit, one switch for choosing if the output voltage is interrupted for 5 s at the end of the 

buffering time or not. 

The operating states of the DC-UPS basic unit are signaled by four LEDs, two floating changeover and one normally-open contacts and a USB-interface  (see Signaling) 

and the control signal “Remote Timerstart” and “Shutdown”.  

Technical Data 

Input quantities: 

Rated input voltage:                                                                  24V DC 

Operating voltage range:                                                  22 to 29V DC 

Max. input current at 24V and capacitor charging:                 17.5A DC 

Max. input current at 24V and charged capacitors:                15.2A DC 

Power loss at 24V and capacitor charging:                        appr. 11.0W 

Power loss at 24V and charged capacitors:                        appr.  9.0W 

Charging time with low charging power and basic unit -2EC41/-2EC51: appr. 110s / 220s 

Charging time with high charging power and basic unit -2EC41/-2EC51: appr. 55s / 120s 

Charging time with low charging power and basic unit -2EC41/-2EC51 and one expansion 

module: appr. 320s / 430s 

Charging time with high charging power and basic unit -2EC41/-2EC51 and one expansion 

module: appr. 160s / 220s 

Output quantities:

 

Rated output DC voltage:             VA1 = 24V DC 

Rated output direct current:         IA1 = 15A DC 

Output current range:                 IA1 = 0 … 15A DC 

Output characteristic of charging regulator: 

The capacitors are charged at an adjustable constant power until the 

end-of-charge voltage is reached. 

End-of-charge voltage:  V = 21.8V DC  

Charging current:            P = 1 or 2A 

Buffering time at 15A load current with basic unit -2EC41/-2EC51: tp = 

3s / 9s (typ.) 

Buffering time at 15A load current with basic unit -2EC41/-2EC51 and 

one add-on expansion module: tp = 15s / 20s (typ.) 

(see diagram 1 on page 7)

 

Settings 

Setting the cut-in threshold:  

If the input voltage drops below the selected cut-in threshold voltage, the DC-UPS basic unit switches over to floating operation. The loads are then supplied solely by the 

DC UPS. The cut-in threshold is set via three DIP-switches (see page 2 for position) according to table 1 (see page 7). 

Setting range: 22.0 to 25.5V DC in 0.5-steps  (delivery state: 22.5V DC 

±

 0.1V), accuracy 

±

  1.8% 

Setting the charging current: 

The expansion module or the internal capacitors are charged via constant current until the set end-of-charge voltage is reached. Charging is then terminated.  The 

setting of the charging current determines how quickly the buffer ready state is restored after a discharging process.  The charging current is set by a DIP switch (position 

see page 2). Setting range: typ. 1A or typ. 2A (delivery state: 1A) 

Setting the operating state ON/OFF:  

Caution:  For normal operation  "ON" state is necessary (delivery state is “OFF”), in order to achieve that use DIP-switch closed or terminals X2.8 and X2.9 

connected with X2.10

 

To prevent the capacitors from being discharged unintentionally (e.g. when the system power is disconnected), the DC-UPS basic unit can be switched with a DIP-switch 

(or a wire jumper (or floating connection) inserted between terminals X2.9 and X2.10) to operating state  "OFF" (delivery state). In the "ON" state (DIP-switch closed or 

terminals X2.8 and X2.9 connected with a floating normally-open contact (V

max

 = 15V DC, I

max

 = 10mA) ), the DC-UPS basic unit is fully functional according to 

specification. In the "OFF" state, the module does not switch over to floating operation when the mains supply is disconnected but remains functional in every other 

respect. If the DC-UPS basic unit is switched to "OFF" in floating operation, it stops operating in floating mode.  

During normal operation, the polling interval for the ON/OFF setting is appr. 20s. 

Setting the buffering time:  

The buffering time is set via five DIP-switches (see page 2 for position) as illustrated in Table 2 (see page 7) in 10s-steps from 5s to 315s. By switch 5 (delivery state 

max. time) you can choose whether floating operation will be terminated after a prespecified period or when the exhaustive discharge threshold of the capacitors (= 

maximum buffering time) is reached (delivery state: max. buffering time). Using the remote signal starts the timer to terminate after a prespecified period.  Once the 

buffering has been terminated, there is no way in which floating operation can be restarted again by altering the switch setting. Only when the input voltage has 

recovered floating operation can be resumed. The buffering time is a appr. 3s with fully charged capacitors and a load current of 15A.  

Interruption of the output voltage: 

By a DIP-switch (see page 2 for position) you can choose if the output voltage is interrupted for 5 s at the end of the buffering time or not (delivery state : no interruption). 

Using the setting  “max. time” an interruption is started by the remote signal.  

Protective and Monitoring Functions

 

Reverse polarity protection:

 

The DC-

UPS basic unit is electronically protected against polarity reversal of the input voltage.

 

Overcurrent and short-circuit protection

In normal operation and floating operation the DC-UPS basic unit is protected by the internal dynamic current 

limitation and the internal static current limitation. Dynamic current limitation limits the output current to typ. 25A. Static dynamic limitation shuts down the output if 

currents are greater than typ. 18A after about 110ms at short-circuit, and after about 200ms at overload. An internal (not accessible) 20A fuse protects the module in the 

event of a fault. In normal operation automatic restart attempts are made approximately every 20s. In floating operation the module shuts down in store mode. Restart 

after return to normal operation.  
 

 

Summary of Contents for SITOP UPS501S

Page 1: ...ng Instructions Notice de service https support industry siemens com cs fr fr view 31762923 Istruzioni operative https support industry siemens com cs it it view 31762923 Instrucciones de servicio https support industry siemens com cs es es view 31762923 操 作 说 明 https support industry siemens com cs cn zh view 31762923 Руководство по эксплуатации https support industry siemens com cs ru ru view 31...

Page 2: ...t der deutsche Text Note These operating instructions do not purport to cover all details of the product nor to provide for every possible contingency that may arise during installation operation or maintenance Subject to change without notice The German text applies in cases of doubt 2V Zuschaltschwelle 1V cut in threshold 0 5V 22V fest eingestellt fixed 2A 1A Ladestrom charging current eingestel...

Page 3: ...dann ausschließlich durch die DC USV versorgt Die Einstellung der Zuschaltschwelle erfolgt mittels 3 Stück DIP Schalter Position siehe Seite 2 gemäß Tabelle 1 siehe Seite 7 Einstellbereich 22 0 bis 25 5 V DC in 0 5V Schritten Auslieferzustand 22 5V DC 0 1V Genauigkeit 1 8 Einstellung des Ladestromes Die Ladung des Erweiterungsmoduls bzw der internen Kondensatoren erfolgt mittels Konstantleistung b...

Page 4: ...ngestellten Überbrückungszeit Tabelle 2 Nach der eingestellten Überbrückungszeit wird der Pufferbetrieb beendet bzw im Normalbetrieb die Ausgangsspannung bei Einstellung Unterbrechung für 5s unterbrochen Der Empfang des Zeichens S Signal Shutdown startet den Timer im DC USV Grundgerät mit der dort eingestellten Überbrückungszeit Tabelle 2 Nach der eingestellten Überbrückungszeit wird das DC USV Gr...

Page 5: ...e DC UPS basic unit switches over to floating operation The loads are then supplied solely by the DC UPS The cut in threshold is set via three DIP switches see page 2 for position according to table 1 see page 7 Setting range 22 0 to 25 5V DC in 0 5 steps delivery state 22 5V DC 0 1V accuracy 1 8 Setting the charging current The expansion module or the internal capacitors are charged via constant ...

Page 6: ...ith the set buffering time table 2 After the set buffering time floating operation ends or during normal operation the output voltage is interrupted for 5 s if disconnection is set Receipt of the character S shutdown signal starts the timer in the DC UPS basic unit with the set buffering time table 2 After the set buffering time the DC UPS basic unit is switched off retentively It is restarted by ...

Page 7: ...n the exhaustive discharge threshold of the capacitors is reached An interruption is started by the remote signal DIP switch Disconnection On On 6 7 8 9 10 gewünschte Pufferzeit buffering time s 5 15 25 35 45 55 65 75 85 95 105 115 125 135 145 155 165 175 185 195 205 215 225 235 245 255 265 275 285 295 305 315 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 ...

Page 8: ... in Ex Bereichen nur mit zusätzlicher Befestigungen verwendet werden um der EN 60079 15 zu genügen WARNING SEPARATE TERMINALS IN NON HAZARDOUS AREAL ONLY ACTUATE SWITCHES IN NON HAZARDOUS AREAS ONLY The signal plug must not be used without additional fixings in explosive atmospheres to fulfill the requirements according EN 60079 15 6EP1935 5PG01 II 3G Ex nA IIC T4 Gc WARNING SEPARATE EXPANSION MOD...

Reviews: