SITOP UPS 500S 

A5E38474162, 08.2016 

 

SITOP UPS 501S 

 

 

English

 

Signaling 

"Normal operation", 

i.e. the input voltage at the DC-UPS basic unit is higher than the set cut-in threshold. The loads are being fed by the line-side power supply. If a 

expansion module is connected, it is fully charged. Under normal operation, the 

green LED

 (o.k.) is illuminated and relay contact X2.2 – X2.3 (o.k.) is closed. 

“>85% charge”, 

i.e. capacitor is loaded more than 85% (

available rest capacity dependent upon aging

). The second green LED (Bat>85%) is illuminated and relay 

contact X2.7 – X2.8 is closed. (second green LED off and relay contact X2.7 – X2.8 open (de-energized position when unit is disconnected) means : Bat<85%, i.e. 

capacitor charge below 85%)  

"Floating operation",

 i.e. the input voltage is lower than the set cut-in threshold. The loads are being supplied by the DC-UPS. In floating operation, the 

yellow LED

 

(Bat) is illuminated and relay contact X2.1 – X2.2 (Bat) closed (de-energized position when unit is disconnected).   

Alarm signal "Buffering not ready": 

When the "Buffering not ready" signal is active, the 

red LED

 (Alarm) is illuminated and relay contact X2.4 – X2.5 (Alarm) closed 

(de-energized position when unit is disconnected). Causes for the "Buffering not ready" state in 

normal operation

 are as follows: "OFF" operating state, defective 

capacitors or capacitor voltage < 7V. The interval for polling the operating states ON/OFF, capacitors or capacitor voltage < 7V, and for activating the relevant signal 

output is 20 s during normal operation. After the end of the failure the signal remains till to the next polling.  

The "Alarm" signal in 

floating operation

 means that the capacitor voltage has dropped to <12V and automatic disconnection is imminent. When the floating operation 

has been finished due to overload, short circuit, exhaustive discharge protection or buffering timeout, the red LED (Alarm) gets dark, but relay contact X2.4 – X2.5 

remains closed. Load rating of relay contacts: 60V DC / 1A or 30V AC / 1A 

 

USB:

 The signals are additionally outputs via a PC-capable USB interface. They are each displayed in the shape of 5 

characters of plain text. The assignment is shown in the  table on the right. A  tool for reading out and processing the 

signals is available free of charge on the Internet at 

http://www.siemens.com/sitop-ups

. This website also contains further 

information about the interface.  

Technical specification: The USB interface is according to specification 2.0, the communication runs only at full speed, 

i.e. 12Mbit/s. The Interface will be supplied by the DC-UPS with +5V (“self-powered”), signal state output every 75ms 

±

 

20%; data output 29ms 

±

 20%, pause 46ms 

±

 20%. The connection to the PC is made by means of a usual 4-wired 

shielded USB-cable with a wave-resistance of 90Ohm, a USB Series”A” connector to the PC and a USB Series “B” 

connector to the DC-UPS and a maximum length of 5m. The cable contains two 28 to 20 AWG “non-twisted” USB-supply 

wires (VBUS and GND) and two 28 AWG “twisted pair” data wires (D+ and D-).   

Pin assignment: Pin1: VBUS (+4.4V to +5.25V DC), transmit data on Pin2 (D-) and Pin3 (D+), Pin4: GND 

Receiving data: Receive of the character “R” (Signal Remote Timerstart) starts the timer of the DC-UPS basic unit with 

the set buffering time (table 2). After the set buffering time, floating operation ends or, during normal operation, the output 

voltage is interrupted for 5 s if "disconnection" is set. Receipt of the character "S" (shutdown signal) starts the timer in the 

DC-UPS basic unit with the set buffering time (table 2). After the set buffering time the DC-UPS basic unit is switched off 

retentively. It is restarted by disconnecting the DC supply voltage for at least 1 s. In combination with a SITOP power 

supply the line voltage has to be interrupted for approx. 10 s for a restart. 

 

 

Signal 

 

Text 

 

Buffering ready  

Buffering not ready 

 

BUFRD 

ALARM 

 

Normal operation 

Not normal operation 

 

DC_OK 

DC_LO 

Not floating operation 

Floating operation 

***** 

*BAT* 

>85% charge 

<85% charge 

BA>85 

BA<85 

 

Environment 

Operating conditions acc. to EN 60721-3-3, climate model 3K3 (relative air 

humidity 5% to 85%, absolute air humidity 1 g/m

3

 to 25 g/m

3

, no condensation) 

Stationary operation, weather protected, pollution degree 2 

Temperature  for storage and shipment:         -40 to +70°C 

Temperature for operation:                              0 to +60°C 

Weight 

6EP1933-2EC41            1.0kg 

6EP1933-2EC51            1.2kg 

6EP1935-5PG01            0.7kg 

Standards 

Degree of protection: IP20 to EN60529 (VDE 0470 Part1) 

Protection class III to EN60950

 

VDE 0100 Part 410 (IEC 364-4-41) 

VDE 0106 Part 1 (IEC 536) 

VDE 0113 Part 1 (EN 60204-1) 

IEC 61131; ; UL 508 / CSA C22.2 File E197259 

The device complies with ATEX directive 2014/34/EU; EN 60079-0; EN 60079-15 

ATEX (see page 8), GL and ABS 

 

 
Installation Instructions 

In order to guarantee effective cooling, the unit must be vertically installed such that the input and output terminals and the incoming air slots are at the bottom. A 

clearance of at least 50 mm must be left above and below the unit. Assembly / disassembly see page 8.

  

To reduce EMI and thermal strain DC-UPS and capacitor modules should be installed at least 50cm away from commutating chokes! Interface (USB) and control leads 

(ON/OFF control circuit) must not be laid directly in parallel to power leads or cables (especially leads between frequency converter and motor or frequency converter and 

commutating choke). 

To minimize EMI the distance to those leads should be at least 10cm. 

 

If the device is to be used in a hazardous zone it must be installed in an enclosure with degree of protection IP54 or higher. This enclosure must comply with the 

requirements of EN 60079-15. 

 

 

Before commencing with the installation or any repair work, switch off the plant main switch and lock it in the "OFF" position. Please read the operating 

instructions for SITOP power. 

 

 

 

Connection and Terminal Assignments 

Terminals 

Function 

Cable cross-

section 

Comments 

X1.1 

Input voltage DC 24V  

1.0 ... 4mm

2

 

Screw-type terminals for screwdriver with 

X1.3, X1.5 

Output voltage DC 24V 

17...11 AWG 

4.5mm blade width 

X1.2/X1.4, X1.6 

Input/output voltage DC 0V 

 

Recommended tightening torque 0.7-0.9Nm 

X2.1,2,3 

Signal: Normal operation / Floating operation 

0.5... 2.5mm

2

 

Screw-type terminals for screwdriver with 

X2.4,5,6 

Signal: Buffering not ready / ready  

20...13 AWG 

3.5mm blade width 

X2.7,8 

Signal: charge >85% 

 

 

X2.9/X2.10 

On/Off jumper (no jumper =Off) 

 

Recommended tightening torque 0.5-0.7Nm 

X3 

Serial interface or USB-interface 

 

See description above 

X10 

Capacitor module 

 

Tailored wire set 

!

 

CAUTION 

The external circuitry of all terminals (including signaling and status contacts) must meet the safety requirements stipulated by 

VDE 0805 (EN 60950): SELV.

 

 

Summary of Contents for SITOP UPS501S

Page 1: ...ng Instructions Notice de service https support industry siemens com cs fr fr view 31762923 Istruzioni operative https support industry siemens com cs it it view 31762923 Instrucciones de servicio https support industry siemens com cs es es view 31762923 操 作 说 明 https support industry siemens com cs cn zh view 31762923 Руководство по эксплуатации https support industry siemens com cs ru ru view 31...

Page 2: ...t der deutsche Text Note These operating instructions do not purport to cover all details of the product nor to provide for every possible contingency that may arise during installation operation or maintenance Subject to change without notice The German text applies in cases of doubt 2V Zuschaltschwelle 1V cut in threshold 0 5V 22V fest eingestellt fixed 2A 1A Ladestrom charging current eingestel...

Page 3: ...dann ausschließlich durch die DC USV versorgt Die Einstellung der Zuschaltschwelle erfolgt mittels 3 Stück DIP Schalter Position siehe Seite 2 gemäß Tabelle 1 siehe Seite 7 Einstellbereich 22 0 bis 25 5 V DC in 0 5V Schritten Auslieferzustand 22 5V DC 0 1V Genauigkeit 1 8 Einstellung des Ladestromes Die Ladung des Erweiterungsmoduls bzw der internen Kondensatoren erfolgt mittels Konstantleistung b...

Page 4: ...ngestellten Überbrückungszeit Tabelle 2 Nach der eingestellten Überbrückungszeit wird der Pufferbetrieb beendet bzw im Normalbetrieb die Ausgangsspannung bei Einstellung Unterbrechung für 5s unterbrochen Der Empfang des Zeichens S Signal Shutdown startet den Timer im DC USV Grundgerät mit der dort eingestellten Überbrückungszeit Tabelle 2 Nach der eingestellten Überbrückungszeit wird das DC USV Gr...

Page 5: ...e DC UPS basic unit switches over to floating operation The loads are then supplied solely by the DC UPS The cut in threshold is set via three DIP switches see page 2 for position according to table 1 see page 7 Setting range 22 0 to 25 5V DC in 0 5 steps delivery state 22 5V DC 0 1V accuracy 1 8 Setting the charging current The expansion module or the internal capacitors are charged via constant ...

Page 6: ...ith the set buffering time table 2 After the set buffering time floating operation ends or during normal operation the output voltage is interrupted for 5 s if disconnection is set Receipt of the character S shutdown signal starts the timer in the DC UPS basic unit with the set buffering time table 2 After the set buffering time the DC UPS basic unit is switched off retentively It is restarted by ...

Page 7: ...n the exhaustive discharge threshold of the capacitors is reached An interruption is started by the remote signal DIP switch Disconnection On On 6 7 8 9 10 gewünschte Pufferzeit buffering time s 5 15 25 35 45 55 65 75 85 95 105 115 125 135 145 155 165 175 185 195 205 215 225 235 245 255 265 275 285 295 305 315 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 ...

Page 8: ... in Ex Bereichen nur mit zusätzlicher Befestigungen verwendet werden um der EN 60079 15 zu genügen WARNING SEPARATE TERMINALS IN NON HAZARDOUS AREAL ONLY ACTUATE SWITCHES IN NON HAZARDOUS AREAS ONLY The signal plug must not be used without additional fixings in explosive atmospheres to fulfill the requirements according EN 60079 15 6EP1935 5PG01 II 3G Ex nA IIC T4 Gc WARNING SEPARATE EXPANSION MOD...

Reviews: