3SK1 devices
5.4 3SK1 input expansions
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
91
5.4.2
Power supply 3SK1230
5.4.2.1
Device features
MLFB:
3SK1230-xAW20
110 ... 240 V AC/DC
(x) 1 = screw-type terminal; 2 = push-in terminal
Device properties:
● Wide-range input: 110 ... 240 V AC/DC
● Rated output voltage: 24 V DC
● Rated output current: 0.6 A
● 1 LED for status display
● Connection interface
● Enclosure width 22.5 mm
● Removable terminals
Note
Due to the output current of the power supply 3SK1230 (= 0.6 A), the use of 3SK1 basic
units with solid-state outputs is only possible to a limited extent. The output current of all
semiconductor outputs can be up to 0.4 A here (depending on the system configuration).
5.4.2.2
Applications
The power supply 3SK1230 generates a stabilized output voltage of 24 V DC from
110 ... 240 V AC/DC. The 3SK1230 power supply can supply the 3SK1 Advanced device
series with 24 V DC via 3ZY device connectors or via the +/– output terminals.
The START pushbutton input "INS" of the 3SK1 device series must be supplied from the
3SK1230 power supply.
NOTICE
Two power supplies in parallel are not permissible! Only one 3SK1230 is permitted per
system configuration.
Summary of Contents for SIRIUS 3SK1
Page 2: ......
Page 10: ...Table of contents 3SK1 safety relays 10 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 186: ...Commissioning 3SK1 safety relays 186 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 258: ...Accessories 3SK1 safety relays 258 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 260: ...Appendix A 1 Correction sheet 3SK1 safety relays 260 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 261: ......