Technical data
13.2 Basic units
3SK1 safety relays
198
Manual, 04/2013, A5E02526190021A/RS-AA/01
3SK1111-.AB..
3SK1111-.AW..
Number of outputs
•
as contact-affected switching element
– as NC contact for reporting function
delayed switching
0
– as NC contact for reporting function
instantaneous switching
1
– as NC contact safety-related delayed
switching
0
– as NC contact safety-related instantaneous
switching
0
– as NO contact for reporting function
delayed switching
0
– as NO contact for reporting function
instantaneous switching
0
– as NO contact safety-related delayed
switching
—
– as NO contact safety-related instantaneous
switching
3
•
as contact-less semiconductor switching
element for reporting function delayed
switching
—
•
as contact-less semiconductor switching
element for reporting function non-delayed
0
•
as contact-less semiconductor switching
element safety-related delayed switching
0
•
as contact-less semiconductor switching
element safety-related non-delayed
0
Stop category according to DIN EN 60204-1
0
Design of the input
•
cascading-input/functional switching
No
•
feedback input
Yes
•
start input
Yes
Design of the electrical connection jumper socket
No
Operating cycles maximum
1/h
360
Switching capacity current of the semiconductor
outputs at DC-13 at 24 V
A
—
Summary of Contents for SIRIUS 3SK1
Page 2: ......
Page 10: ...Table of contents 3SK1 safety relays 10 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 186: ...Commissioning 3SK1 safety relays 186 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 258: ...Accessories 3SK1 safety relays 258 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 260: ...Appendix A 1 Correction sheet 3SK1 safety relays 260 Manual 04 2013 A5E02526190021A RS AA 01 ...
Page 261: ......