③
Place the connectors on the link module (U
i
= 690 V), as shown in the figure, into the top main
conductor terminals on the contactor.
④
Screw the main conductor terminals tight on the contactor.
⑤
Place the reversing contactor assembly with the fitted link module onto the DIN rail adapter and
guide the reversing contactor assembly onto the motor starter protector from below. Insert the
connectors on the link module into the bottom main conductor terminals on the motor starter
protector.
⑥
Screw the reversing contactor assembly to the DIN rail adapter. The reversing contactor assembly
sits tight on the adapter.
Tightening torque: 1.5 ... 1.6 Nm
⑦
Screw the main conductor terminals of the motor starter protector tight.
⑧
Attach the wiring modules for connecting the main current paths to the contactors from below.
Disassembling the feeder from the DIN rail adapter
To disassemble the feeder, unscrew the screws and pull the feeder down to remove it.
Mounting
7.3 Assembly and disassembly with different mounting systems
SIRIUS 3RA Load Feeders
Equipment Manual, 02/2022, A5E03656507520A/RS-AC/004
85
Summary of Contents for SIRIUS 3RA
Page 26: ...Functions SIRIUS 3RA Load Feeders 26 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Page 120: ...Connection SIRIUS 3RA Load Feeders 120 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...
Page 122: ...Operation SIRIUS 3RA Load Feeders 122 Equipment Manual 02 2022 A5E03656507520A RS AC 004 ...