Standard mapping 2-1
7SJ61...7SJ63, 7SJ65, 6MD63 PROFIBUS-DP – Bus mapping
C53000-L1840-B006-02
2-10
2.2.1.19 Measurement supervision
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
17/2
Fail I Superv.
1 = Failure: General current supervision
161
17/3
Failure <Sum>I
1 = Failure: Current summation
162
17/4
Fail Ph. Seq.
1 = Failure: Phase sequence
171
17/5
MeasSup OFF
1 = Measurement supervision is switched OFF
197
2.2.1.20 Set point alarms
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
17/6
SP. Op Hours>
1 = Set point operating hours
272
17/7
SP. IA dmd>
1 = Set point phase A dmd>
273
18/0
SP. IB dmd>
1 = Set point phase B dmd>
274
18/1
SP. IC dmd>
1 = Set point phase C dmd>
275
18/2
SP. I1 dmd>
1 = Set point positive sequence I1 dmd>
276
18/3
SP. |Pdmd|>
1 = Set point |Pdmd|>
277
18/4
SP. |Qdmd|>
1 = Set point |Qdmd|>
278
18/5
SP. |Sdmd|>
1 = Set point |Sdmd|>
279
18/6
SP. 37-1 alarm
1 = Set point 37-1 undercurrent alarm
284
18/7
SP. PF(55)alarm
1 = Set point 55 power factor alarm
285
2.2.1.21 Status annunciations
•
Ref. to chap. 1.5.7 for additional notes regarding "Stop data transmission".
Offset
Designation of the
SIPROTEC objects
Comments
Internal
object no.
19/0
>No Volt
1 = Binary input “No voltage (fuse blown)" is active
–
19/1
DataStop
1 = "Stop data transmssion" is active
–
19/2
Test mode
1 = Test mode is active
–
19/3
Cntrl Auth (device 7SJ63/6MD63)
Control authority
(0 = REMOTE, 1 = LOCAL)
–
19/4
ModeLOCAL (device 7SJ63/6MD63)
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
–
19/5
ModeREMOTE
Control mode REMOTE
(0 = LOCKED , 1 = UNLOCKED)
–
19/6
Cntrl Auth (device 7SJ61/62)
Control authority
(0 = REMOTE, 1 = LOCAL)
–
19/7
ModeLOCAL (device 7SJ61/62)
Control mode LOCAL
(0 = LOCKED, 1 = UNLOCKED)
–
1
Not used in the 7SJ61, 7SJ62.
2
Not used in the 7SJ63, 7SJ65, 6MD63.