3 Mounting and Commissioning
340
7UT613/63x Manual
C53000-G1176-C160-2
3.1
Mounting and Connections
General
WARNING!
Warning of improper transport, storage, installation, and application of the
device.
Non-observance can result in death, personal injury or substantial property damage.
Trouble free and safe use of this device depends on proper transport, storage, instal-
lation, and application of the device according to the warnings in this instruction
manual.
Of particular importance are the general installation and safety regulations for work in
a high-voltage environment (for example, VDE, IEC, EN, DIN, or other national and
international regulations). These regulations must be observed.
3.1.1
Configuration Information
Prerequisites
For installation and connections the following conditions must be met:
The rated device data has been tested as recommended in the SIPROTEC 4 System
Description and their compliance with the Power System Data is verified.
Connection Vari-
ants
General diagrams are shown in the Appendix A.2. Connection examples for current
and voltage transformer circuits are provided in Appendix A.3. It must be checked that
the settings for configuration (Subsection 2.1.3) and the Power System Data (Subsec-
tion 2.1.4) match the connections to the device.
Protected Object
The setting of the
protected object
(address
105
) must correspond to the object to
be protected. An incorrect setting may cause unforeseeable reactions by the device.
Please note that for auto-transformers
PROT. OBJECT
=
autotransf.
and not
3-phase transf.
must be set. For
single-phase transformer
, the centre phase L2 is
not used.
Currents
Connection of the CT currents depends on the mode of application.
With three-phase connection the three phase currents are assigned to the measuring
locations. Connection examples for the various protected objects are provided in the
Appendix A.3. Please refer also to the Appendix A.2 for the general diagrams that
apply to this device. Check that the measuring locations are correctly assigned to the
sides of the protected object and to the measuring inputs on the device.
With two-phase connection of a single-phase transformer the centre phase will not be
used. Appendix A.3 shows connection examples. Even if there is only one current
transformer, both phases (
I
L1and
I
L3) will be used. Also observe the General Dia-
grams in annex A.2 that apply to the current device.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...