![Siemens SIPROTEC 5 7UM85 Manual Download Page 31](http://html.mh-extra.com/html/siemens/siprotec-5-7um85/siprotec-5-7um85_manual_382660031.webp)
Assessment of Functional Safety According to
IEC 61508
The 7UM85 devices have been subjected to an assessment of functional safety according to the standard
IEC 61508.
The following table shows the assessment results of the 8 variants for the 7UM85 device. All the assessment
values are based on an ambient temperature of 40 °C (104 °F) according to the standard IEC 60255-1.
i
i
NOTE
If you need assessment values which are based on other ambient temperatures, contact the Customer
Support Center. You can find more information of the Customer Support Center in
.
Item
Variant 1 Variant 2 Variant 3 Variant 4 Variant 5 Variant 6 Variant 7 Variant 8
Diagnostic coverage
87 %
85 %
89 %
82 %
82 %
82 %
84 %
86 %
Safe fail fraction (SFF)
94 %
93 %
94 %
91 %
91 %
92 %
92 %
93 %
Undetected, dangerous failure
rate (λ
DU
)
3866
4856
3513
6858
6285
5212
4222
4283
Detected, dangerous failure
rate (λ
DD
)
25 783
27 741
29 336
31 007
29 206
24 492
22 535
25 940
Undetected and detected safe
failure rate (λ
SU
and λ
SD
)
29 883
32 646
30 990
37 836
36 091
31 651
28 888
30 901
Probability of failure on
demand (PFD)
1.7 ⋅ 10
-2
2.1 ⋅ 10
-2
1.6 ⋅ 10
-2
3.0 ⋅ 10
-2
2.7 ⋅ 10
-2
2.3 ⋅ 10
-2
1.9 ⋅ 10
-2
1.9 ⋅ 10
-2
Safety integrity level (SIL)
1
Hardware architecture
1oo1
Hardware failure tolerance
0
Type of subsystem
B
Proof test interval
1 year
Mean time to restore
8 h
Base module: C PS201 + IO202
Variant 1: Base IO205 + IO206
Variant 2: Base IO205 + IO207
Variant 3: Base IO231 + IO206
Variant 4: Base IO207 + IO207 + IO207
Variant 5: Base IO207 + IO207 + IO201
Variant 6: Base IO207 + IO207
Variant 7: Base IO207 + IO206
Variant 8: Base IO201 + IO205
5
SIPROTEC 5, Additional Information on the Protection of Explosion-Proof Motors with Type of Protection Increased Safety e,
Manual
31
C53000-H5050-C078-1, Edition 03.2019