Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
242
T-CBtest-dead
P.System Data
1
0.00 .. 30.00 sec
0.10 sec
Dead Time for CB test-
autoreclosure
302
CHANGE
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another
Setting Group
402A WAVEFORM-
TRIGGER
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
403A WAVEFORM DATA
Osc. Fault Rec.
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
410
MAX. LENGTH
Osc. Fault Rec.
0.30 .. 5.00 sec
2.00 sec
Max. length of a Wave-
form Capture Record
411
PRE. TRIG. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.25 sec
Captured Waveform Prior
to Trigger
412
POST REC. TIME
Osc. Fault Rec.
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after
Event
415
BinIn CAPT.TIME
Osc. Fault Rec.
0.10 .. 5.00 sec
0.50 sec
Capture Time via Binary
Input
610
FltDisp.LED/LCD
Device
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
625A T MIN LED HOLD
Device
0 .. 60 min
0 min
Minimum hold time of
latched LEDs
640
Start image DD
Device
image 1
image 2
image 3
image 4
image 5
image 6
image 1
Start image Default
Display
1103 FullScaleVolt.
P.System Data
2
1.0 .. 1200.0 kV
400.0 kV
Measurement: Full Scale
Voltage (100%)
1104 FullScaleCurr.
P.System Data
2
10 .. 5000 A
1000 A
Measurement: Full Scale
Current (100%)
1107 P,Q sign
P.System Data
2
not reversed
reversed
not reversed
P,Q operational measured
values sign
1130A PoleOpenCurrent
P.System Data
2
1A
0.05 .. 1.00 A
0.10 A
Pole Open Current
Threshold
5A
0.25 .. 5.00 A
0.50 A
1131A PoleOpenVoltage
P.System Data
2
2 .. 70 V
30 V
Pole Open Voltage
Threshold
1135 Reset Trip CMD
P.System Data
2
CurrentOpenPole
Current AND CB
Pickup Reset
CurrentOpenPole
RESET of Trip Command
1136 OpenPoleDetect.
P.System Data
2
OFF
Current AND CB
w/ measurement
w/ measurement
open pole detector
1150A SI Time Man.Cl
P.System Data
2
0.01 .. 30.00 sec
0.30 sec
Seal-in Time after
MANUAL closures
Functions, Settings, Information
E.2 Settings
288
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...