Configuring the HMI system
2.5 Configuring user alarms
HMI Advanced (IM4)
Commissioning Manual, 03/2009, 6FC5397-0DP10-3BA0
83
2.5
Configuring user alarms
2.5.1
Classifying user alarms
Number ranges
The following alarm numbers are available for the cycle alarms, compile cycle alarms, and
PLC alarms:
Numerical range
Designation
Effect
Deletion
60000 - 60999
Cycle alarms (Siemens)
Display, interlocking NC start
Reset
61000 - 61999
Display, interlocking NC start, no motion
after executing the pre-decoded blocks
Reset
62000 - 62999
Display
Cancel
63000 - 64999
Reserved
65000 - 65999
Cycle alarms (user)
Display, interlocking NC start
Reset
66000 - 66999
Display, interlocking NC start, no motion
after executing the pre-decoded blocks
Reset
67000 - 67999
Display
Cancel
68000 - 69000
Reserved
70000 - 79999
Compile-cycle alarms:
400000 - 499999
PLC alarms general
500000 - 599999
PLC alarms for channels
600000 - 699999
PLC alarms for axes and spindles
700000 - 799999
PLC alarms for users
800000 - 899999
PLC alarms for sequence
cascades/graphs
Reference: Function Manual Basic Functions: PLC basic program (P3 sl)
Selecting the language for alarm texts
If alarm texts are to be configured in languages other than those already available in the
control, then a softkey "language selection" can be configured. The name of the text file is
used to assign language-specific user alarm texts. The appropriate code and the extension
.com are added to the user file name entered in MBDDE.INI.
Summary of Contents for SINUMERIK
Page 6: ...Preface Base software and HMI Advanced 6 Commissioning Manual 03 2009 6FC5397 0DP10 3BA0 ...
Page 96: ......
Page 562: ...Index Expanding the user interface Index 4 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Page 566: ...Table of contents Online Help HE1 4 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 ...
Page 598: ...Online Help HE1 Commissioning Manual 11 2006 6FC5397 0DP10 0BA0 36 ...