● Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
①
Shield busbar
②
Shielded cable
③
Mounting clip
Figure 6-1
Shield connection using a clip
NOTICE
Impaired functionality as a result of damaged or incorrectly connected cable shields
Incorrect connection or damaging of the cable shield can impair the function of the system.
● Handle the cable shield carefully.
● Ensure that the cable shield is correctly connected.
● Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum
impedance and through the largest possible surface area.
①
Shield busbars
②
Cables
③
Terminals
Figure 6-2
Bridging shield gaps
Electrical connection
6.2 Electromagnetic compatibility
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE
89
Summary of Contents for Sinamics SM150 6SL3845-2NN41-8AD0
Page 2: ...01 08 2019 09 08 V32 00 ...
Page 98: ...Start up SINAMICS SM150 6SL3845 2NN41 8AD0 98 Operating Instructions Rev 201908010908 EXAMPLE ...
Page 187: ......
Page 190: ......
Page 192: ......