Example: Changing analog output 0 from current to voltage output – / +10 V and setting the characteristic
;
Voltage output present at terminal 1, ground is at terminal 2
S>@
Set TM31.AO_type [analog output 0] to between -10 and +10 V.
S>@
Set TM31.AO_char. x1 to 0.00%.
S>@
Set TM31.AO_char.
1 to 0.000 V.
S>@
Set TM31.AO_char. x2 to 100%.
S>@
Set TM31.AO_char. y2 to 10.000 V.
Factory setting
Digital output
Terminal
Factory setting
DO0
X542: 2,3
"Pulses enabled"
DO1
X542: 5,6
"No fault"
DI/DO8
X541: 2
"Ready for switching on"
DI/DO9
X541: 3
DI/DO10
X541: 4
DI/DO11
X541: 5
8.5.2.2
Additional settings for analog outputs
Two signals are freely available for each TM31, which can be used to output the analog signals.
Additional setting parameters for analog output 0 (AO0)
Parameter
Value
Adjustment range
p4077[0]
Analog outputs, characteristic value x1
-1000.00 to +1000.00%
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Operation
8.5 Functions
SINAMICS SM150 6SL3845-2NN41-8AD0
Operating Instructions Rev.201908010908 EXAMPLE
113