Description
2
2.1
Description of the PGU and the features implemented in the
simulation model
Power generating unit (PGU), type SINAMICS PCS comprises the following components:
•
Active Interface Module of the SINAMICS S120 series of Siemens AG
•
Active Line Module of the SINAMICS S120 series of Siemens AG
•
An energy source connected to the device DC connection.
The hardware-related closed-loop control of the PGU is realized in the CU320-2 Control
Module.
The SINAMICS firmware was extended to include a DCC chart to implement the requirements
of VDE-AR-N 4110.
Additional notes are provided in the associated documentation of function expansion "Drive
Control Chart" (DCC), see SINAMICS documentation
https://support.industry.siemens.com/cs/ww/en/ps/6SL3054-0FC../man
Description of the features implemented in the SINAMICS PCS simulation model
The simulation model models the following:
•
Grid reactor and inverter
•
Closed-loop control of the active and reactive current in undisturbed operation and for
dynamic grid faults
•
Closed-loop control of the DC voltage
•
Closed-loop reactive power control
Here, only the direct setpoint input is taken into consideration.
A simulation in the cos phi closed-loop control/Q(U)/Q(P) operating mode is not part of the
model.
•
Controlled reduction of the active power for overfrequency conditions and when specified
by the grid operator
•
Grid protection and/or grid monitoring
The model can be adapted to various PGU application conditions. The grid connection voltage
and the rated current of the PGU can be parameterized.