Maintenance and service
6.4 Replacing components
Air-Cooled Chassis Power Units - supplement to Motor Module 6SL3320-1TG41-5AA3
70
Equipment Manual, 10/2020, A5E50422764A
Note
Crane lifting lugs on power block, frame size JX
For power blocks, frame size JX, the front crane lifting lug is located behind the busbar.
6.4
Replacing components
6.4.1
Safety information
WARNING
Improper transport and installation of devices and components
Serious injury or even death and substantial material damage can occur if the devices are
not transported or installed properly.
•
Transport, mount, and remove the devices and components only if you are qualified to
do so.
•
Take into account that the devices and components are in some cases heavy and top-
heavy; take the necessary precautionary measures.
The weights of the individual power blocks are listed in the corresponding section.
6.4.2
Messages after replacement of DRIVE-CLiQ components
After DRIVE-CLiQ components are replaced (Control Interface Module, TM31, SMCxx) when
service is required, generally no message is output after power-up, since an identical
component is identified and accepted as component when the system boots.
The reason for this is that an identical component is detected and accepted as spare part
when running-up. If, unexpectedly, a fault message of the "topology fault" category is
displayed, then when replacing a component, one of the following faults/errors should have
occurred:
•
A Control Interface Module with different firmware data was installed.
•
When connecting-up DRIVE-CLiQ cables, connections were interchanged.