Error messages
TM15 / TM17 High Feature Operating Manual
54
Commissioning Manual, 05/2009
Error correction
If problems arise during commissioning of the TM15 or TM17 High Feature, please verify the
following:
●
Make sure that the planned application is permitted. Note the information in the
SIMOTION constraint list (see SCOUT CD).
●
Check the firmware version of the TM15/TM17 High Feature and update it if necessary.
●
Delete the Fast I/O configuration via SCOUT. Select, for example, the "D435" controller in
the project tree. Right-click to open the context menu and select FastIO --> Delete
configuration. Then execute Transfer to HW Config in the SINAMICS configuration
screen form.
●
If necessary, delete the user data on the CompactFlash Card and completely reload the
project. Then execute Copy RAM to ROM.
●
Restart (power on or hot restart) the SINAMICS or SIMOTION D device. The new I/O
channel parameters do not take effect until you execute the restart.