Features
Type
Flexible, with wire-end ferrule without plastic
sleeve
0.2 mm² … 2.5 mm²
Flexible, with wire-end ferrule with plastic
sleeve
0.2 mm² … 1.5 mm²
AWG / kcmil
22 … 12
Stripped length
6 … 7 mm
Tool
Screwdriver 0.5 x 3 mm (M2.5)
Tightening torque
0.4 to 0.5 Nm
Max. current carrying capacity, incl. loop-through
20 A (15 A per UL/CSA)
Max. cable length
10 m
Interface assignments
Table 4-11
Power supply X124
Pin
Signal name
Signal type
Meaning
1
P24
VI
Power supply 24 V
2
P24
VI
24 V power supply
3
G
VO
Ground
4
G
VO
Ground
Signal type: VI = Voltage input (power supply) VO = Voltage output (power supply)
Note
The 24 V is looped through via the 24 V connector. In this case, pin 1 is jumpered with pin 2,
and pin 3 is jumpered with pin 4.
Position of power supply interface
*
3RZHUVXSSO\FRQQHFWRU
Figure 4-5
Power supply interface
Interfaces
4.5 Power supply
SIMOTION D4x5
Manual, 04/2014
59