①
Customer connecting cable
②
Connection bar
See also
6.4.5
Use of aluminum conductors
If you are using aluminum conductors, then comply with the following:
● Use only cable lugs that are suitable for connecting aluminum conductors.
● Immediately before inserting the aluminum conductor, remove the oxide layer from the
contact areas on the conductor and/or the mating piece. Do this using a brush or file.
● Then grease the contact areas immediately using neutral Vaseline. This prevents a new
oxide layer from forming.
NOTICE
Aluminum flow due to contact pressure
Aluminum flows following installation due to the contact pressure. The connection using
clamping nuts can loosen as a result. The contact resistance increases, obstructing the
current from being conducted. This can result in fire and material damage to the machine
– or even in total failure, as well as material damage to the plant or system due to machine
failure.
● Retighten the clamping nuts after approximately 24 hours and then again after
approximately four weeks. Make sure that the terminals are de-energized before you
tighten the nuts.
For terminal box &1XB7.. with aluminum connection bars, you can also connect copper cables
using copper cable lugs.
Electrical connection
6.4 Inserting and routing the cables
SIMOTICS T-1FW4 Heavy Duty 1FW4407-1KM81-1BC0-Z
Operating Instructions 11/2018
57