02.00
Parameter list
SIEMENS AG 6RX1700-0AD76
11-45
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P494
*
FDS
Motor temperature analog 2 (temperature sensor at terminals 204 /
205): Tripping of alarm or fault message
Motor temperature grasped with KTY84
0
Monitoring deactivated
1
Alarm (A029) at temperature > P491
2
Fault message (F029) at temperature > P492
3
Alarm (A029) at temperature > P491 and
fault message (F029) at temperature > P492
Motor temperature grasped with PTC thermistor
0
Monitoring deactivated
1
Alarm message (A029) when operating point of PTC thermistor
is reached
2
Fault message (F029) when operating point of PTC thermistor
is reached
3
Illegal setting
0 to 3
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P495
*
FDS
Brush length sensing: Tripping of alarm or fault message
0
No brush length sensing (terminal 211 is not scanned)
1
Binary brush length sensing (terminal 211 is scanned)
Alarm (A025) in response to 0 signal
2
Binary brush length sensing (terminal 211 is scanned)
Fault message (F025) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P496
*
FDS
Bearing condition: Tripping of alarm or fault message
0
No bearing condition sensing (terminal 212 is not scanned)
1
Bearing condition sensing (terminal 212 is scanned)
Alarm (A026) in response to 1 signal
2
Bearing condition sensing (terminal 212 is scanned)
Fault message (F026) in response to 1 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P497
*
FDS
Air flow: Tripping of alarm or fault message
0
No air flow monitoring (terminal 213 is not scanned)
1
Air flow monitoring (terminal 213 is scanned)
Alarm (A027) in response to 0 signal
2
Air flow monitoring (terminal 213 is scanned)
Fault message (F027) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P498
*
FDS
Temperature switch: Tripping of alarm or fault message
0
No temperature switch connected (terminal 214 is not scanned)
1
Temperature switch connected (terminal 214 is scanned)
Alarm (A028) in response to 0 signal
2
Temperature switch connected (terminal 214 is scanned)
Fault message (F028) in response to 0 signal
0 to 2
1
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
11.25 Configuring of torque shell input
P500
*
BDS
Source for torque setpoint for slave drive
Selection of the connector to be injected as the torque setpoint for a
slave drive
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=170
Type: L2
P052 = 3
P051 = 40
Offline
P501
*
BDS
Source for additional torque setpoint
Selection of connector to be injected as the additional torque setpoint
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
Summary of Contents for SIMOREG DC Master 6RA7018-6DS22
Page 10: ...Contents 02 00 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instrctions ...
Page 14: ...Safety Information 02 00 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instrctions ...
Page 22: ...Type spectrum 02 00 2 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 142: ...Connections 02 00 6 64 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 180: ...Start Up 02 00 7 38 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 392: ...Faults Alarms 02 00 10 28 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 610: ...Applications 02 00 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 612: ...Appendix 02 00 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 614: ...Appendix 02 00 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 615: ......