02.00
Parameter list
SIEMENS AG 6RX1700-0AD76
11-65
SIMOREG DC Master Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P746
*
Source for enabling of "Main actual value" analog input
Selection of binector to control enabling of the analog input ("1" state =
enabled)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.36 Analog
outputs
(see also Section 8, Sheets G115 and G116)
Analog output terminals 12 / 13 (actual current display)
P749
*
Control word for terminal 12 (actual current display)
0
Output with correct sign
(positive voltage: Current in torque direction MI)
(negative voltage: Current in torque direction MII)
1
Output of absolute value (positive voltage only)
2
Output with sign, inverted
(positive voltage: Current in torque direction MII)
(negative voltage: Current in torque direction MI)
3
Output of absolute value, inverted (negative voltage only)
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Analog output terminals 14 / 15
P750
*
Source for output value at analog output 1
Selection of connector whose value is to applied to the analog output
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Online
P751
*
Mode of signal injection at analog output 1
0 = Injection of signal with correct sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P752
Filtering time for analog output 1
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P753
Normalization of analog output 1
y V
x
P
[ ]
%
= ∗
753
100
x = Normalization input (corresponds to filtering output)
y = Normalization output (corresponds to output voltage at analog output
with offset = 0)
-200.00 to 199.99
[V]
0.01V
Ind: None
FS=10.00
Type: I2
P052 = 3
P051 = 40
Online
P754
Offset for analog output 1
-10.00 to 10.00
[V]
0.01V
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
Analog output terminals 16 / 17
P755
*
Source for output value at analog output 2
Selection of connector whose value is to applied to the analog output
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Online
P756
*
Mode of signal injection at analog output 2
0 = Injection of signal with correct sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P757
Filtering time for analog output 2
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Summary of Contents for SIMOREG DC Master 6RA7018-6DS22
Page 10: ...Contents 02 00 0 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instrctions ...
Page 14: ...Safety Information 02 00 1 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instrctions ...
Page 22: ...Type spectrum 02 00 2 8 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 142: ...Connections 02 00 6 64 Siemens AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 180: ...Start Up 02 00 7 38 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 392: ...Faults Alarms 02 00 10 28 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 610: ...Applications 02 00 17 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 612: ...Appendix 02 00 18 2 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 614: ...Appendix 02 00 18 4 SIEMENS AG 6RX1700 0AD76 SIMOREG DC Master Operating Instructions ...
Page 615: ......