Wiring
6.2 Additional rules and regulations for operation of the S7-1500/ET 200MP with fail-safe modules
Automation system
System Manual, 12/2017, A5E03461182-AE
127
Additional requirements for actuators
The fail-safe output modules test the outputs at regular intervals. The F-module briefly
switches off the activated outputs and, if necessary, switches on the deactivated outputs.
You can assign the maximum duration of the test pulses (dark and light period) with
parameters.
High-speed actuators may briefly drop out or be activated during this test. If your process
does not tolerate this, set the pulse duration of the light or dark test correspondingly or use
actuators that have sufficient lag.
WARNING
If the actuators switch voltages greater than 24 V DC (for example, 230 V DC), safe
electrical isolation must be ensured between the outputs of a fail-safe output module and
the components carrying a higher voltage (in accordance with EN 60664-1:2010).
This is generally the case for relays and contactors. Particular attention must be paid to this
issue for semiconductor switching devices.
Technical specifications of sensors and actuators
Refer to the manuals of the fail-safe modules for technical specifications to assist you in
selecting sensors and actuators.
Summary of Contents for Simatic S7-1500/ET 200MP
Page 1: ......