Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Level
IEC
60068-21-1
Vibration
2g @ 10-150 Hz
IEC
60068-21-2
Shock
30 g @ 11 ms
IEC
60068-2-78
Humidity (Damp
Heat, Steady State)
Test Cab
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC
60068-2-14
Change of Temperature
Test Nb
5 Cycles, -40 to 85°
C (40 to 185° F)
IEC
60255-21-2
Bump
10 g @ 16 ms
Class 1
IEC
60255-21-3
Seismic
Method A, Class 2
Class 1
RUGGEDCOM RSG2100P
Installation Manual, 04/2022, C79000-G8976-1041-20
47