System diagnostics
9.2 XML/PLC error messages
SIMATIC RF600
System Manual, 06/2019, J31069-D0171-U001-A22-7618
475
"ER"
LED
XML/
LED
(hex)
PLC block
(hex)
Error description
2 Hz
0xC1 0xE4FE81 The specified tag field of the transponder is unknown.
2 Hz
0xCA 0xE4FE8A General error
2 Hz
0xCB 0xE4FE8B No or bad configuration data/parameters were transferred.
Possible cause:
•
You are accessing a read point that is not configured.
--
0xCC 0xE4FE8C
•
Communication error between Ident profile and communications module. Handshake
error.
–
UDT of this communications module is overwritten by other program sections
–
Check parameter settings of communications module in the UDT
–
Check the Ident profile command that caused this error
–
Start "INIT" after correcting the error
•
Backplane bus / PROFIBUS DP / PROFINET error occurred
This error is only indicated when access monitoring has been enabled in the
PROFIBUS configuration.
–
Backplane bus / PROFIBUS DP / PROFINET bus connection was interrupted (wire
break on the bus; bus connector on the communications module was briefly un-
plugged)
–
Backplane bus / PROFIBUS DP / PROFINET master no longer addressing commu-
nications module
–
Execute "INIT"
–
The communications module has detected a frame interruption on the bus. The
backplane bus, PROFIBUS or PROFINET may have been reconfigured (e.g. with
HW Config or TIA Portal)
2 Hz
0xCD 0xE4FE8D
•
Firmware error
Possible cause: The firmware update was not run completely.
•
Internal communications error of the communications module/reader
–
Connector contact problem on the communications module/reader
–
Hardware of the communications module/reader has a defect;
→
Send in communi-
cations module/reader for repair
–
Start "INIT" after correcting the error
•
Internal monitoring error of the communications module/reader
–
Program execution error on the communications module / reader
–
Turn the power supply of the communications module/reader off and on again
–
Start "INIT" after correcting the error
2 Hz
0xCE 0xE4FE8E The current command was aborted by the "WRITE-CONFIG" ("INIT" or "SRESET") com-
mand for the bus connector was pulled.
Possible causes:
•
Communication with the transponder was aborted by "INIT".
•
This error can only be reported if there is an "INIT" or "SRESET".
2 Hz
0x51
0xE5FE01 Incorrect sequence number order (SN) on the reader/communications module.
--
0x52
0xE5FE02 Incorrect sequence number order (SN) in the Ident profile