background image

Preface, Contents

Product Description

1

Starting Up the Push Button
Panel

2

Control Bit Assignment

3

Installation

4

Unit Description OEM PP32

5

Unit Description OEM
PP32/OP17

6

Attach Labeling Strips

7

Spare Parts

8

Technical Data

A

System Messages

B

Hardware Test

C

Siemens Worldwide

D

Index

Release 08/98

OEM PP32,
OEM PP32/OP17
Push Button Panels

Equipment Manual

SIMATIC HMI

6AV3991–1XB00–0AB0

Summary of Contents for SIMATIC OEM PP32

Page 1: ... 3 Installation 4 Unit Description OEM PP32 5 Unit Description OEM PP32 OP17 6 Attach Labeling Strips 7 Spare Parts 8 Technical Data A System Messages B Hardware Test C Siemens Worldwide D Index Release 08 98 OEM PP32 OEM PP32 OP17 Push Button Panels Equipment Manual SIMATIC HMI 6AV3991 1XB00 0AB0 ...

Page 2: ...achine which is to accommodate this component is in conformity with the guideline 89 392 EEC Faultless and safe operation of the product presupposes proper transportation proper storage erection and installation as well as careful operation and maintenance SIMATICR is a registered trademark of Siemens AG Some of the other designations used in these documents are also registered trademarks the owne...

Page 3: ...tton Panels 2 Step by step instructions on how to configure a Push Button Panel 3 Detailed information on the interrelationship between the Push Button Panel and PLC 4 Mechanical and electrical installation of the Push Button Panels 5 6 Unit description of the various Push Button Panel versions 7 Information on labelling 8 Information on spare parts Appendices Technical data system messages hardwa...

Page 4: ...C BASIC Hotline Local time Mon Fri 8 00 to 18 00 Tel 49 911 895 7000 Fax 49 911 895 7002 E mail simatic support nbgm siemens de Local time Mon Fri 8 00 to 17 00 Tel 1 423 461 2522 Fax 1 423 461 2231 E mail simatic hotline sea siemens com Local time Mon Fri 8 30 to 17 30 Tel 65 740 7000 Fax 65 740 7001 E mail simatic singnet com sg SIMATIC Premium Hotline chargeable SIMATIC Card required Times Mon ...

Page 5: ...at http www ad siemens de simatic from the fax polling service on 08765 93 02 77 95 00 S Up to date product information and downloads for practical use can be found on the internet at http www ad siemens de support html 00 from the Bulletin Board System BBS in Nuremberg SIMATIC Cus tomer Support Mailbox on 49 911 895 7100 For calling up the mailbox you should use a modem with up to V 34 28 8 kBaud...

Page 6: ...iv OEM Push Button Panel Equipment Manual Release 08 98 Preface ...

Page 7: ...ction 2 6 2 3 Configuring Keys LEDs 2 9 2 3 1 Configuring Keys LEDs When Using MPI Connection 2 11 2 3 2 Configuring Keys LEDs When Using PROFIBUS DP Connection 2 12 2 4 Coordinating the Push Button Panel and PLC 2 13 3 Control Bit Assignment 3 1 4 Installation 4 1 5 Unit Description OEM PP32 5 1 6 Unit Description OEM PP32 OP17 6 1 7 System MessagesSpare Parts 7 1 A Technical Data A 1 A 1 General...

Page 8: ...vi OEM Push Button Panel Equipment Manual Release 08 98 Contents ...

Page 9: ...t the necessity of PLC programs S Short stroke keys with surface illumination according to the LED colors S Additional 24 V digital inputs and outputs S All short stroke keys and digital 24 V inputs can also be individually configured as switches S Integrated lamp and key test S Central release input to lock all operating actions S Integrated flash timing S Color coding for LEDs such as red green ...

Page 10: ...tandard documentation S Consistency with standard Push Button Panels with regard to electronics function configuration bus connection S Further variations complying to customer requirements are possible on request e g installation of additional elements complying to company standards norms rotary knobs handwheel continuous potentiometer for fast intuitive modification of set values numeric display...

Page 11: ...ly ready to operate Various options can also be activated by adjusting certain parameters Each key LED digital input and output can be individually adapted according to specific requirements No special configuration software is necessary for the Push Button Panel All adjustment of the settings is carried out either directly on the Push Button Panel or by means of the PLC configuration software All...

Page 12: ...N BF SIMATIC OEM PP32 OP17 Hardware OEM PP32 OEM PP32 OP17 Short stroke keys surface Number of short stroke keys 32 keys surface illumination keys Inputs Outputs Number of digital inputs 16 p p Number of digital outputs 16 Installable ope rating elements Number of 22 5 mm ele ments which can be inte grated 12 1 SHUTDOWN right 8 2 SHUTDOWN left Release input Lock operation of the Push Button Panel ...

Page 13: ...P32 OP17 OEM PP32 Hardware Communication SIMATIC S5 Communication SIMATIC S5 PROFIBUS DP 4 PROFIBUS DP 4 SIMATIC S7 M7 SIMATIC S7 M7 MPI 4 MPI PROFIBUS DP 4 4 PROFIBUS DP 4 Data transmission Baud rate Max 12 MBaud Integrated standard unit OP17 Product Description ...

Page 14: ...board OP17 Standard keyboard PP32 22 5 mm elements PP32 System keyboard OP17 Example Figure 1 1 Front view OEM PP32 OP17 The Push Button Panels are all equipped with a keyboard containing short stroke keys The individual keys can be configured in respect of their function as either switches or keys Function momentary contact switch The corresponding bit in the PLC is set as long as the key is pres...

Page 15: ...nd the bits are set in the PLC After restarting the system following a power failure all the bits are set to 0 Additional 22 5 mm elements can be connected using the digital inputs and outputs Non connected digital inputs are automatically set to 0 The release input serves to lock the Push Button Panel A key operated switch can be connected here for example The release input permits switching betw...

Page 16: ... actions initiated on the Push Button Panel and changing bit status in the PLC Key Contact Release input pressed open not pressed closed Time Function as momentary contact switch Bit in PLC 1 0 Key Function as switch Bit in PLC Contact Release input Time pressed 1 open not pressed 0 closed Pulse diagrams Product Description ...

Page 17: ...sh Button Panel digital outputs are set to 1 After pressing any key when in operating mode Lamp Key test S the LED lamps go out for the period in which the key is pressed S all the Push Button Panel digital outputs are set to 0 This is valid for the period in which the key is pressed All the keys and digital inputs can be tested in this way In order that no unwanted signals are transmitted to the ...

Page 18: ...1 10 OEM Push Button Panel Equipment Manual Release 08 98 Product Description ...

Page 19: ...00 Highest station address 126 Number of MPI masters 1 The following table provides an overview of the possibilities for modifying the defined system settings Intention Procedure Chap ters Modify MPI address Set MPI address on Push Button Panel 2 1 Change baud rate Change baud rate on Push Button Panel 2 1 Change data area type Change data area type on Push Button Panel 2 1 Configure Push Button P...

Page 20: ...ocedure Chap ters Set connection type DP Set connection type DP on the Push Button Panel 2 1 Change DP slave address Change the DP slave address on the Push Button Panel 2 1 Change baud rate Change baud rate on Push Button Panel 2 1 Configure Push Button Panel properties which deviate from Set parameter in the configu ration software 2 3 properties which deviate from pre adjusted system settings r...

Page 21: ...ification in the current menu level and skip for ward to the next menu level The key has no func tion in the bottom menu level In configuration mode this key serves to skip back to the superordinated menu level The key has no function in the top menu level Caution Any modifications carried out to the set tings in the current menu level are not stored In configuration mode this key serves to skip f...

Page 22: ...nd underlined alternatives indicate the predefined system settings CONNECTION DP MPI SLAVE ADR BAUDRATE PP MPI ADR RACK NO BAUDRATE DATA MB DB PARAM DB PLC ADR SLOT NO HSA PLC TYPE 2 3 400 DP MPI 200 400 NUMBER OF MPI MASTER DB DW DB MW MB DEFAULT YES NO 3 187 5 KBaud 100 0 2 100 0 0 3 126 1 3 1500 KBaud 300 Starting Up the Push Button Panel ...

Page 23: ...or Data Block DB MW Defines the number of the first reserved memory word for the Push Button Panel DB Defines the number of the data block in which the data area for the Push Button Panel is reserved DW Defines the number of the first reserved data word for the Push Button Panel in the data block PARAM DB Defines the number of the configuring data block PLC ADR Defines the address of the PLC to wh...

Page 24: ...ated in the PLC which contains the configuration data for the Push Button Panel The structure of this data block parameter is illustrated in Chapter 2 3 1 The number of the configuring data block must be specified when configuring the Push Button Panel 2 2 2 PROFIBUS DP Connection When connection type PROFIBUS DP is used the Push Button Panel must be installed in the PROFIBUS configuration softwar...

Page 25: ...eck whether your system is already provided with the special GSD file required for your Push Button Panel To do this call in the configuration software COM PROFIBUS SIMATIC S5 or HW CONFIG SIMATIC S7 COM PROFIBUS SIMATIC S5 Check whether an entry exists in the hard ware family SIMATIC or SIMATIC PP for your Push Button Panel HW CONFIG SIMATIC S7 Check whether an entry exists in the hard ware catal...

Page 26: ...from directory GSD on the disk to the path S7DATA GSD in the STEP 7 installation and 2 all the files from directory BITMAPS on the disk to the path S7DATA NSBMP in the STEP 7 installation 3 Update the GSD files available in the system COM PROFIBUS SIMATIC S5 Select the command Update DDB Files from the menu File HW CONFIG SIMATIC S7 Select the command Update DDB Files from the menu Options After t...

Page 27: ...e Lamp test function The keys are numbered from right to left in rows beginning at the top right moving down The value 0 deactivates the Lamp test Value range 0 to total number of keys System default setting Lamp test assigned to Key 1 top right Function keys It is possible to define whether a key on the keyboard should function as a key or switch Function momentary contact switch The correspondin...

Page 28: ...data block Byte n Byte n 1 Control bits for LED 1 Bit 7 Bit 0 Two successive configuration bits in one configuring data block define the way in which the status of the control bits are displayed The following table illustrates the effects of the various combinations of configuration bits on the LED display Configuration bits Control bits LED xx xx xx 00 01 10 11 00 01 10 11 11 11 11 off lights gre...

Page 29: ...M PP32 Entry for OEM PP32 OP17 Byte 0 0 Byte 1 0 Byte 2 P Byte 3 P Byte 4 1 Byte 5 7 Byte 6 4 Byte 7 8 Byte 8 2 Byte 9 4 Byte 10 0 Byte 11 0 Byte 12 Pulse extension Byte 13 Lamp test key Byte 14 Function key 1 8 Byte 15 Function key 9 16 Byte 16 Function of key 17 24 Byte 17 Function key 25 32 Byte 18 Function digital input 1 8 Byte 19 Function digital input 9 16 Byte 20 Mode LED 1 4 Byte 21 Mode ...

Page 30: ...Chapter 2 2 the configuration software COM PROFIBUS SIMATIC S5 or HW CONFIG SIMATIC S7 can be used to define all the settings for the Push Button Panel COM PROFIBUS Call in dialog box Slave properties by double clicking on the PP symbol When it appears click on button Configure HW CONFIG Select property page Configure in dialog box Object properties Starting Up the Push Button Panel ...

Page 31: ...k In order to use the above mentioned functions a con figuring data block must be created as described in Chapter 2 3 1 The first byte is reserved The figure below illustrates the structure of byte n 1 The individual bits are described underneath the figure 7 6 5 4 3 2 1 0 Address n 1 Life bit Start bit Bit 0 Start bit 1 Push Button Panel has started up The bit is set by the Push Button Panel on c...

Page 32: ...2 14 OEM Push Button Panel Equipment Manual Release 08 98 Starting Up the Push Button Panel ...

Page 33: ...wing figures clarify the numeration of keys LEDs and digital inputs outputs on the Push Button Panel and their links to bits in the PLC Keys 8 1 Bit 7 Bit 0 T8 T1 T16 T9 Byte n Byte n 1 32 25 T24 T17 T32 T25 Byte n 2 Byte n 3 Figure 3 1 Numeration of keys on the Push Button Panel 1 16 Digital Inputs DI Bit 7 Bit 0 DI8 DI1 DI16 DI9 Byte n Byte n 1 Figure 3 2 Numeration of the digital inputs on the ...

Page 34: ... Bit 7 Bit 0 Byte n Byte n 1 Byte n 2 Byte n 4 DO8 DO1 DO8 DO1 DO16 DO9 DO16 DO9 Figure 3 4 Numeration of the digital outputs on the Push Button Panel The following table indicates the data area for keys LEDs digital inputs and digital outputs of the Push Button Panel in the PLC Data area OEM PP32 OEM PP32 OP17 Keys 4 Bytes Digital inputs 2 Bytes LEDs 8 Bytes Digital outputs 4 Bytes Total 18 Bytes...

Page 35: ...LED or display element Digital inputs 1 8 Digital inputs 9 16 Structure of the data in the PLC Element assignment 0 Keys 1 8 Keys 9 16 Keys 17 24 Keys 25 32 Key 1 LED 1 Digital output 10 Digital input 5 Key 24 LED 24 0 1 8 16 7 10 17 Bit Assignment LEDs 1 8 LEDs 9 16 LEDs 17 24 LEDs 25 32 Digital outputs 1 8 Digital outputs 9 16 Byte 1 8 16 Digital inputs 1 16 DI Digital outputs 1 16 DO Figure 3 5...

Page 36: ...3 4 OEM Push Button Panel Equipment Manual Release 08 98 Control Bit Assignment ...

Page 37: ...ms do not switch the Push Button Panel on until it is absolutely dry S To prevent the Push Button Panel overheating during operation ensure the air vents in the housing are not covered following installation S The Push Button Panel was function tested before shipping If a fault oc curs however please enclose a full account of the fault when returning the unit Degree of Protection 4 ...

Page 38: ... housing Alternative openings are provided on the sides of the Push Button Panel to enable the installation of several units beside each other without leaving any gaps between them Front panel Push Button Panel Ê 3 Secure the Push Button Panel in the front panel Ë from the rear using a screwdriver Note Do not overtighten the screws to avoid damage Front panel Ë Push Button Panel Front panel thickn...

Page 39: ...nstalled 4 Insert a screwdriver or similarly appropriate tool from the rear through the elongated hole Ê in the middle of the selected snap out hole Use the screwdriver to lever the metal piece out where the 22 5 mm element is to be inserted 5 Cut the foil corresponding to the opening which appears in the front section of the Push Button Panel 6 Insert the 22 5 mm element in the opening in the fro...

Page 40: ...ges outside this range may cause malfunctions Connect the grounding connection of the Push Button Panel to the cabinet ground To do this use the grounding screw supplied with the Push Button Panel Push Button Panel 24 V 0 V Input Output Push Button Panel 24 V 0 V Warning No safety related functions may be realized using the Push Button Panel Cable Voltage supply Grounding connection Connection of ...

Page 41: ...late 5 5 125 226 330 30 60 Frame 322 The OEM PP32 requires a mounting cut out WxH of 290 mm x 318 5 mm Note The installation depth of the Push Button Panel is dependent on the type of connection cable to the PLC It does not correspond to the outer dimensions of the unit Ensure the cable has a sufficient bending radius Unit dimensions Mounting cut out 5 ...

Page 42: ...module Display Bus connection MPI PROFIBUS DP Voltage supply 24 V 0 V Digital 24 V inputs DI1 DI16 Digital 24 V outputs DO1 DO16 Release input Grounding connection Figure 5 1 Assignment of elements on the rear side of the OEM PP32 Rear view Unit Description OEM PP32 ...

Page 43: ... view Front view 470 305 0 7 8 9 4 5 6 B A C 1 2 3 E D F DEL HELP INS ESC ENTER SHIFT ACK F1 F2 F3 F4 F5 F6 F7 F8 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16 HELP V SHIFT RUN BF PP32 OP17 295 461 PP cover OP cover Front plate 5 5 125 226 317 462 470 30 46 60 Frame Unit dimensions 6 ...

Page 44: ...xH of 290 x 458 all specifications in mm Note The installation depth of the Push Button Panel is dependent on the type of connection cable to the PLC It does not correspond to the outer dimensions of the unit Ensure the cable has a sufficient bending radius Mounting cut out Unit Description OEM PP32 OP17 ...

Page 45: ...age supply 24 V 0 V Digital 24 V inputs DI1 DI16 Digital 24 V outputs DO1 DO16 Release input Grounding connection IF1A IF1B IF2 Battery connection Power supply Grounding connection OP17 Push Button Panel Figure 6 1 Assignment of elements on the rear side of the OEM PP32 OP17 Rear view Unit Description OEM PP32 OP17 ...

Page 46: ...6 4 OEM Push Button Panel Equipment Manual Release 08 98 Unit Description OEM PP32 OP17 ...

Page 47: ...ext program and printing out on a standard printer The disk supplied with this document contains a directory SLIDES in which the file SLIDES DOC is stored This is a text file in Word for Windows 6 0 format with which the labeling strips for the Push Button Panel can be printed in the correct size The following table contains the dimensional specifications for producing the labeling strips Size OEM...

Page 48: ...7 2 OEM Push Button Panel Equipment Manual Release 08 98 0 72 0 102 8 195 2 226 0 253 0 133 6 164 4 Figure 7 2 Text positions for 22 5 mm elements OEM PP32 and OEM PP32 OP17 Attach Labeling Strips ...

Page 49: ... the display in both normal operation and hardware test mode In this case the memory module must be replaced The complete customized units are not stocked in stores or supply works Stocking must be carried out by the customer Customers themselves must pro vide a stores for units required to prevent or in the event of a system shut down With the exception of the OEM PP32 keyboard no spare parts are...

Page 50: ...8 2 OEM Push Button Panel Equipment Manual Release 08 98 Spare Parts ...

Page 51: ...nel S Rear panel IP65 IP20 Weight approx kg Approx 3 0 Approx 4 8 24 V voltage supply OEM PP32 OEM PP32 OP17 Rated voltage VDC 24 Permissible range VDC 18 to 30 Typical power consumption at 24 V1 0 4 A OP17 part 0 4 A PP32 part 0 4 A Starting current inrush I2t 30x10 3 A2s OP17 part 30x10 3 A2s PP32 part 30x10 3 A2s Fuse type internal Electronic fuse Reverse battery protection Yes 1 Power consumpt...

Page 52: ...g standards Interference immunity EN 50082 1 OEM PP32 OEM PP32 OP17 Static discharge contact discharge EN 61000 4 2 Class 3 RF irradiation EN 61000 4 3 Class 3 Pulse modulation ENV 50204 900 MHz 5 MHz RF conduction ENV 50141 Class 3 Burst interference ENV 61000 4 4 Class 3 Radio interference EN 50081 2 OEM PP32 OEM PP32 OP17 RFI suppression EN 55011 Class A A 2 Digital inputs and outputs 24 V digi...

Page 53: ...utput DO1 to DO4 S output DO5 to DO8 S output DO9 to DO12 S output DO13 to DO16 16 4 Group 1 Group 2 Group 3 Group 4 Potential isolation Short circuit protection Yes Permissible loads Resistive Lamps Inductive Max inductive power 200 mWs Output voltage S with signal 0 S with signal 1 Max 2 V idling Min voltage supply 3 V Output current S with signal 0 S with signal 1 Max 1 mA Max 500 mA per group ...

Page 54: ...s S with shielded cables 1 m 1 m Release input OEM PP32 OEM PP32 OP17 Potential isolation from internal circuitry Input voltage S Rated value S release on entry S lock on entry 24 V DC 0 5 V 15 30 V Input current with entry locked Typ 2 mA at 24 V A 3 Interface assignment Assignment of the 9 pin Sub D socket Pin Assignment 1 2 3 Data B 4 5 GND pot free 6 5V pot free 7 8 Data A 9 Bus connection PRO...

Page 55: ...ton Panel 7 or 17 Version identification of the Push Button Panel The following table should help to determine the cause of Error LED signals Signal Cause Remedy LED flashes Normal operation The unit is in Lamp Key test mode Terminate the Lamp test by S releasing the corresponding key or S resetting the corresponding bits in the PLC LED lights up Hardware test mode Hardware test mode is displayed ...

Page 56: ...ration of the interface on the Push Button Panel PP START PROFIBUS DP connection There is a connection fault Check the network configuration and the configuration of the interface on the Push Button Panel PP START MPI connection Connection to the defined MPI ad dress cannot be established Check the following settings in the Push Button Panel interface configuration S BAUDRATE S PLC ADR S RACK NO a...

Page 57: ... any key OK In Hardware Test mode this key serves the function in the current menu level The results of the indi vidual tests appear as they are completed OK ERROR A fault has occurred The functional unit tested is defective In Hardware Test mode this key serves to skip back to the superordinated menu level The key has no function in the first menu level In Hardware Test mode this key serves to sk...

Page 58: ...ion with key combination ESC OK KEYB TEST After pressing a key on the keyboard the corresponding LED lights up orange Terminate the function with key or EEPROM TEST EEPROM OK ASPC2 TEST ASPC2 OK DIGIO TEST DI xxxx DO xxxx xxxx Status of the digital inputs and out puts as hexadecimal values KEY TEST xx Status of the release input KEYB ID xxxx Keyboard identifica tion PP17 I 2010 PP17 I 4020 EXT MOD...

Page 59: ... Federal Republic of Germany Aachen Augsburg Bayreuth Berlin Bielefeld Bonn Bremen Brunswick Chemnitz Coblenz Cologne Constance Darmstadt Dortmund Dresden Duisburg Düsseldorf Erfurt Essen Frankfurt am Main Freiburg Hamburg Heilbronn Karlsruhe Kassel Kempten Allg Kiel Laatzen Leipzig Lingen Magdeburg Mainz Mannheim Munich Münster Westf Nuremberg Osnabrück Regensburg Rostock Saarbrücken Siegen Stutt...

Page 60: ...d S Nicosia Czech Republic Siemens AG S Brno S Mladá Boleslav S Prague Denmark Siemens A S S Copenhagen Ballerup Finland Siemens Oy S Espoo Helsinki France Siemens S A S Haguenau S Lille Seclin S Lyon Caluire et Cuire S Marseille S Metz S Paris Saint Denis S Strasbourg S Toulouse Great Britain Siemens plc S Birmingham Walsall S Bristol Clevedon S Congleton S Edinburgh S Glasgow S Leeds S Liverpool...

Page 61: ...arsaw Portugal Siemens S A S Albufeira S Coímbra S Lisbon Amadora S Matosinhos S Porto Romania Siemens birou de consultatii tehnice S Bukarest Russia Siemens AG or Mosmatic S Moscow Siemens AG S Ekaterinburg Slovak Republic Siemens AG S Bratislava Slovenia Siemens d o o S Ljubljana Spain Siemens S A S Barcelona S Bilbao S Gijón S Granada S La Coruña S Las Palmas de Gran Canaria S León S Madrid S M...

Page 62: ... Siemens Ltd S Mafekeng Egypt Siemens Technical Office S Cairo Mohandessin Siemens Technical Office S Alexandria EGEMAC S A E S Cairo Mattaria Ethiopia Addis Electrical Engineering Ltd S Addis Abeba Ivory Coast Siemens AG S Abidjan Libya Siemens AG Branch Libya S Tripoli Morocco SETEL Société Electrotechnique et de Télécommunications S A S Casablanca Mozambique Siemens Liaison Office S Maputo Nami...

Page 63: ...ntatives of Siemens AG in America Argentina Siemens S A S Bahía Blanca S Buenos Aires S Còrdoba S Mendoza S Rosario Bolivia Sociedad Comercial é Industrial Hansa Ltda S La Paz Brazil Siemens S A S Belém S Belo Horizonte S Brasilia S Campinas S Curitiba S Fortaleza S Pôrto Alegre S Recife S Rio de Janeiro S Salvador de Bahia S São Paulo S Vitória Canada Siemens Electric Ltd S Montreal Québec S Toro...

Page 64: ...mens Industrial Automation Inc Automation Division S Alpharetta GA Numeric Motion Control S Elk Grove Village Illinois Uruguay Conatel S A S Montevideo Venezuela Siemens S A S Caracas S Valencia The following table lists all Siemens Companies and Representatives of Siemens AG in Asia Bahrain Transitec Gulf S Manama Bangladesh Siemens Bangladesh Ltd S Dhaka Brunei S Brunei Darussalam Hong Kong Siem...

Page 65: ...eed Associates S Muscat Pakistan Siemens Pakistan Engineering Co Ltd S Islamabad S Karachi S Lahore S Peshawar S Quetta People s Republic of China Siemens AG Representation S Beijing S Guangzhou S Shanghai Philippine Islands Maschinen Technik Inc MATEC S Manila Qatar Trags Electrical Engineering and Air Conditioning Co S Doha Saudi Arabia Arabia Electric Ltd Equipment S Al Khobar S Jeddah S Riyadh...

Page 66: ...S Dubai Vietnam OAV Representative Office S Hanoi Yemen Arab Republic Tihama Tractors Engineering Co Ltd or Siemens Resident Engineers S Sanaa The following table lists all Siemens Companies and Representatives of Siemens AG in Australia Australia Siemens Ltd S Adelaide S Brisbane S Melbourne S Perth S Sydney New Zealand Siemens Ltd S Auckland S Wellington Australia Siemens Worldwide ...

Page 67: ...ng keys 2 11 2 12 Configuring LEDs 2 11 2 12 Connect Additional elements 4 4 Ground 4 4 Connectable elements A 2 Connection type 2 1 2 2 MPI 2 1 2 5 2 6 2 11 2 13 PROFIBUS DP 2 2 2 5 2 6 2 12 Connection types 1 3 Contact discharge A 2 Control bit Assignment 3 1 Coordination PLC and Push Button Panel 2 13 D Data technical A 1 Data area 2 1 2 5 Data block 2 5 2 6 2 11 Data transmission Baud rate 1 5...

Page 68: ...it 2 13 List System messages B 1 Load current A 4 Loads permissible A 3 M Marker area 2 6 Memory area 3 2 Memory module 1 3 2 3 8 1 B 2 Memory requirements 3 2 Memory word 2 1 2 5 Messages B 1 B 2 Mounting cut out 4 2 A 1 OEM PP32 5 1 OEM PP32 OP17 6 2 Mounting depth A 1 MPI address 2 1 2 5 2 6 MPI Connection 2 1 2 5 2 6 2 11 MPI master 2 1 2 5 N Number of inputs A 2 O Operating concept 1 7 Operat...

Page 69: ...presentatives D 1 Signals Error LED B 1 Slave address 2 2 2 5 Slot 2 5 Snap out opening 4 3 Spare Parts 8 1 Standard unit integrated 1 5 Start bit 2 13 Starting current inrush A 1 Starting Up 2 1 Static discharge A 2 Station address highest 2 1 2 5 Steuerung konfigurieren 2 6 Storage requirements 2 6 Switching frequency A 3 System messages List B 1 System settings 2 5 modify 2 1 2 2 MPI connection...