Lightning protection category for buildings
Caution
For outdoor installation, the antenna may be fitted only within the lightning protection
zones O/E or 1. These lightning protection zones are prescribed by the lightning
protection spherical radius.
The EMV lightning protection zone concept
Caution
The EMV lightning protection zone concept is to be observed. To avoid large induction
loops a lightning protection equipotential bonding is to be used. If the antenna or
antenna cable is installed near to the lightning protection system, the minimum
distances to the lightning protection system must be observed. If this is not possible,
insulated installation as described in VDE V 0185 Sections 1 to 4, in its current
version, is essential.
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
•
Reorient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected.
•
Consult the dealer / installer or an experienced radio/TV technician for help.