Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (Non-Condensing),
55 °C (131 °F), 6 cycles
IEC 60068-78
Humidity (Damp Heat, Steady State)
10 days @ 55 °C (131 °F)
and 93% Relative Humidity
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
IEC 60255-21-2
Shock
30 g @ 11 ms
IEC 60255-21-3
Seismic
Method A, Class 2
IEC 60068-1-14
Change of Temperature
5 Cycles (-40 to 85 °C or -40 to 185 °F)
62
RUGGEDCOM RX1400