Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 61000-4-18
Damped Oscillatory Wave
Slow Damped
2.5 kV Common
100 kHz or 1 MHz
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
DC Power Ports
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
IEC 60255-5
HV Impulse
DC Power Ports
5 kV
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RX1400 meets Class 1 requirements for copper ports, which allows
for temporary communication loss.
Test
Description
Test Levels
Signal Ports
HV Impulse
DC Power Ports
5 kV
Signal Ports
Dielectric Strength
DC Power Ports
2828 VDC or 2 kV
Signal Ports
DC Power Ports
Fast Transient (SWC)
Earth Ground Ports
± 4 kV @ 2.5 kHz, 5 kHz
Signal Ports
2.5 kV Common mode @1 MHz
Oscillatory (SWC)
DC Power Ports
2.5 kV Common Mode
1 kV Differential Mode @ 1 MHz
Radiated RFI
Enclosure ports
35 V/m
Enclosure Contact
± 8 kV
IEEE 1613
ESD
Enclosure Air
± 15 kV
IEEE 1613.1/
IEC 61000-4-10
Damped Oscillating
Magnetic Field
Enclosure Ports
100 A/m for 1 s (100 kHz and 1 MHz)
Environmental Type Tests
Test
Description
Test Levels
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-1
Cold Storage
Test Ab
-40 °C (-40 °F), 16 hours
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-2
Dry Heat Storage
Test Bb
85 °C (185 °F), 16 hours
RUGGEDCOM RX1400
Installation Manual, 01/2021, C79000-G8976-1103-17
61